Plan Review Notes
Plan Review Notes For Permit 02111690
Permit Number 02111690
Review Stop M
Sequence Number 2
Notes
Date Text
2003-04-09 00:00:00DENIED:1ST REVIEW DONE BY H. MOSER
  
 1.PLANS DO NOT INDICATE RETURN AIR
 DUCTS OR GRILLES.
  
 2.RETURN AIR DUCTS OR TRANSFER AIR
 REQUIRED FROM THE BEDROOM AREAS AS PER
 2001 FBC(M) 601.4.
  
 PLEASE NOTE SUFFICIENT SPACE SHALL BE
 PROVIDED FOR CONSTRUCTION, INSPECTION,
 CLEANING AND MAINTENANCE OF THE AIR
 HANDLING UNITS.4" MINIMUM AROUND THE
 AHU AS PER 2001 FBC(M) 603.1.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.