| 2003-04-09 00:00:00 | DENIED:1ST REVIEW DONE BY H. MOSER | | | | | | 1.PLANS DO NOT INDICATE RETURN AIR | | | DUCTS OR GRILLES. | | | | | | 2.RETURN AIR DUCTS OR TRANSFER AIR | | | REQUIRED FROM THE BEDROOM AREAS AS PER | | | 2001 FBC(M) 601.4. | | | | | | PLEASE NOTE SUFFICIENT SPACE SHALL BE | | | PROVIDED FOR CONSTRUCTION, INSPECTION, | | | CLEANING AND MAINTENANCE OF THE AIR | | | HANDLING UNITS.4" MINIMUM AROUND THE | | | AHU AS PER 2001 FBC(M) 603.1.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|