Notes
Date Text
2003-04-03 00:00:00************** UNSAT ***************
  
 PLEASE SEE ORIG NOTES
  
 1)NOTE: PLEASE SEE 225-31 FOR MEANS
 OF DISC AT ANY BLDG FED FROM ANOTHER.
 PLEASE ALSO CLARIFY HOW BRANCH CIRCUITS
 WOULD BE FED TO DETACHED BLDG W/OUT
 PANELS IN MAIN HOUSE?
  
 2)NOTE: PLEASE SEE 250-31 FOR GROUNDING
 OF DETACHED BLDGS.
  
 3)NOTE: PLEASE SEE NFPA-72 8-1.4.2,
 PLANS STILL MISSING SD`S INSIDE ALL
 SLEEPING ROOMS. PLEASE ALSO NOTE, SD
 ON EACH LEVEL OF A MULTI-LEVEL RES HOUSE
 IN THE IMMEDIATE VICINITY OF STAIRWAY
 NFPA-72 2-5.2.1.6
 PLEASE ALSO NOTE, SD`S ARE NOT PERMITTED
 IN KITCHEN, MAY BE HEAT IF DESIRED.
 SD`S ARE TO BE A MIN OF 3' FROM BATH
 DOORS.
  
 4)NOTE: PLEASE SEE 210-52 FOR RECEPT
 SPACING ALONG WALLS.PLEASE SEE THAT
 THERE ARE SOME MISSING ON SECOND FLOOR.
 ALSO 210-52E REAR OF DWELLING
 5)NOTE: PLEASE SEE MISSING RECEPT FOR
 A/C COND UNITS. 210-63
  
 6)NOTE: PLEASE CLARIFY RISER, SHOWS
 HAND WRITTEN CHANGES THAT A& B ARE DISC`
 S? PANELS SHOW MLO? PLEASE INDICATE
 IF MCB AND PLEASE REF BACK TO NOTE#1.
  
 7)NOTE: PLEASE SEE FS/FAC 61G15-23.002,
 61G1-16.004, PLEASE SEE INFORMATION
 REQ`D FOR TITLE BLOCK ON PLANS THAT ARE
 SIGNED AND SEALED BY ARCH'S/ ENGINNERS.
 471/481.
  
 8)NOTE: PLEASE SEE MAX OCP FOR AHU#2,
 7.5KW @150%. MAX AT 2P50A. SHOWN AT 60A.
 PLEASE VERIFY.
 PLEASE ALSO SHOW ACCES TO AHU#1, SHOWN
 W/ ALL FOUR SIDE ENCLOSED? 110-26
  
 PLEASE ALSO SEE FS 553.80(2)(B) FOR
 PLANS AND RESPECT TO DESIGN PROFESSIONAL
 -S.. SEE LETTER ATTACHED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  