| 2003-04-03 00:00:00 | ************** UNSAT *************** |
| | |
| | PLEASE SEE ORIG NOTES |
| | |
| | 1)NOTE: PLEASE SEE 225-31 FOR MEANS |
| | OF DISC AT ANY BLDG FED FROM ANOTHER. |
| | PLEASE ALSO CLARIFY HOW BRANCH CIRCUITS |
| | WOULD BE FED TO DETACHED BLDG W/OUT |
| | PANELS IN MAIN HOUSE? |
| | |
| | 2)NOTE: PLEASE SEE 250-31 FOR GROUNDING |
| | OF DETACHED BLDGS. |
| | |
| | 3)NOTE: PLEASE SEE NFPA-72 8-1.4.2, |
| | PLANS STILL MISSING SD`S INSIDE ALL |
| | SLEEPING ROOMS. PLEASE ALSO NOTE, SD |
| | ON EACH LEVEL OF A MULTI-LEVEL RES HOUSE |
| | IN THE IMMEDIATE VICINITY OF STAIRWAY |
| | NFPA-72 2-5.2.1.6 |
| | PLEASE ALSO NOTE, SD`S ARE NOT PERMITTED |
| | IN KITCHEN, MAY BE HEAT IF DESIRED. |
| | SD`S ARE TO BE A MIN OF 3' FROM BATH |
| | DOORS. |
| | |
| | 4)NOTE: PLEASE SEE 210-52 FOR RECEPT |
| | SPACING ALONG WALLS.PLEASE SEE THAT |
| | THERE ARE SOME MISSING ON SECOND FLOOR. |
| | ALSO 210-52E REAR OF DWELLING |
| | 5)NOTE: PLEASE SEE MISSING RECEPT FOR |
| | A/C COND UNITS. 210-63 |
| | |
| | 6)NOTE: PLEASE CLARIFY RISER, SHOWS |
| | HAND WRITTEN CHANGES THAT A& B ARE DISC` |
| | S? PANELS SHOW MLO? PLEASE INDICATE |
| | IF MCB AND PLEASE REF BACK TO NOTE#1. |
| | |
| | 7)NOTE: PLEASE SEE FS/FAC 61G15-23.002, |
| | 61G1-16.004, PLEASE SEE INFORMATION |
| | REQ`D FOR TITLE BLOCK ON PLANS THAT ARE |
| | SIGNED AND SEALED BY ARCH'S/ ENGINNERS. |
| | 471/481. |
| | |
| | 8)NOTE: PLEASE SEE MAX OCP FOR AHU#2, |
| | 7.5KW @150%. MAX AT 2P50A. SHOWN AT 60A. |
| | PLEASE VERIFY. |
| | PLEASE ALSO SHOW ACCES TO AHU#1, SHOWN |
| | W/ ALL FOUR SIDE ENCLOSED? 110-26 |
| | |
| | PLEASE ALSO SEE FS 553.80(2)(B) FOR |
| | PLANS AND RESPECT TO DESIGN PROFESSIONAL |
| | -S.. SEE LETTER ATTACHED. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |