| Plan Review Notes For Permit 02111690 |
| Permit Number |
02111690 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-01-11 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) SHT 16 SANITARY RISER DIAGRAM DOES | | | NOT MEET CODE. PLEASE SEE RED LINE | | | CORRECTIONS. TABLE 906.1 VENT FOR TUB | | | EXCEEDS MAXIMUM DISTANCE OF FIXTURE TRAP | | | FROM VENT. DRAIN LINE FROM BATH #2 SHALL | | | TIE IN DOWN STREAM OF POWDER ROOM. NO | | | TRAP SHOWN FOR WASH MACHINE. | | | 2) SHT 16 PLEASE SHOW THERMAL EXPANSION | | | CONTROL, (EXPANSION TANK), AT WATER | | | HEATER DETAIL. SECTION 607.3.2 | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|