Plan Review Notes
Plan Review Notes For Permit 02111690
Permit Number 02111690
Review Stop P
Sequence Number 1
Notes
Date Text
2003-01-11 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT 16 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE. PLEASE SEE RED LINE
 CORRECTIONS. TABLE 906.1 VENT FOR TUB
 EXCEEDS MAXIMUM DISTANCE OF FIXTURE TRAP
 FROM VENT. DRAIN LINE FROM BATH #2 SHALL
 TIE IN DOWN STREAM OF POWDER ROOM. NO
 TRAP SHOWN FOR WASH MACHINE.
 2) SHT 16 PLEASE SHOW THERMAL EXPANSION
 CONTROL, (EXPANSION TANK), AT WATER
 HEATER DETAIL. SECTION 607.3.2
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377