Plan Review Notes
Plan Review Notes For Permit 02111682
Permit Number 02111682
Review Stop E
Sequence Number 1
Notes
Date Text
2002-12-03 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASENOTE, PLANS REFERENCE
 NOTES TO THE "96" NEC. PLEASE NOTE,
 WE ARE UNDER THE 99 NEC.
  
 2)NOTE: PLEASE SEE 700-12 FOR CIRCUITING
 FOR EM/EX LTS.
  
 3)NOTE: PLEASE CLARIFY, WATER HEATER
 SHOWN ON PLANS WITH A DISC AND PANEL
 SCHEDULE SHOWS A LOCK ON DEVICE. PLEASE
 NOTE CERTAIN "LOCK ON " DEVICES ARE NOT
 ACCEPTABLE. JUST A NOTE.
  
 4)NOTE: PLEASE NOTE, NOTE#9 ON E-1
 MENTIONS TO CONTACT "LL" REP. PLEASE
 NOTE, SHOULD READ FPL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLANS ARE IN GOOD SHAPE WITH
 ONLY MINOR ITEMS.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372