| Plan Review Notes For Permit 02111609 |
| Permit Number |
02111609 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-12-11 00:00:00 | ************* UNSAT *************** | | | | | | 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS | | | WITH NEW HEAT PUMP LOAD BEING ADDED AND | | | SHOW ALL EXISTING LOADS ALSO. | | | PLEASE SHOW SIZE OF EXIST. SERVICE. | | | 215-5 | | | | | | 2)NOTE: PLEASE SEE RISER DIAGRAM FOR | | | WIRING OF HEATER. PLEASE NOTE SUBMITTAL | | | SHOW NEW HEAT PUMP MIN CIRCUIT AMPACITY | | | AT 40AMPS, AND RISER SHOWS #12'S? | | | PLEASE SEE 310-16 FOR RATING OF WIRE. | | | AND OCP. | | | | | | 3)NOTE: PLEASE SEE 250-122 FOR SIZING | | | EQUIPMENT GROUND TO HEATER. SHOWN AS #12 | | | ALSO. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|