| 2006-05-01 00:00:00 | BUILDING REVISION 2ND CHECKLIST: |
| | 1- WIND LOAD CRITERIA: CLEARLY LIST ALL |
| | FIVE ITEMS AS REQUIRED BY SECTION |
| | 1606.1.7 FBC 2001. |
| | |
| | 2- SHEET A-5: AREA CALCULATIONS ARE |
| | WRONG. RECALCULATE ALL AREAS AND REVISE |
| | AS REQUIRED TO UPDATE VALUATION AND |
| | SQUARE FEET ACCORDINGLY. |
| | |
| | 3- AFTER CALCULATIONS ARE REVISED. BRING |
| | BACK DRAWINGS TO PALM BEACH COUNTY FOR |
| | RE-STAMPING. |
| | |
| | 4- PROVIDE PRODUCT APPROVAL FOR: |
| | A) ENTRY DOORS AS SHOWN ON PLANS. |
| | B) 9'X8' GARAGE DOOR. |
| | C) CASEMENT WINDOWS ON SECOND FLOOR. |
| | |
| | 5- PROVIDE CUT SHEETS FOR CASEMENT |
| | WINDOWS SIZES SHOWN ON 2ND FLOOR TO |
| | VERIFY COMPLIANCE WITH EGRESS OPENING. |
| | SEC. 1005.4.4 FBC 2001. |
| | |
| | 6- ARCHITECT TO PROVIDE COMPLETE TILE |
| | FASTENING SPECIFICATIONS AS REQUIREDBY |
| | SEC. 104.2.1.1 CITY AMENDMENTS TO FBC |
| | 2001. |
| | TYPICAL WALL SECTIONS SPECIFY "ATTACH |
| | CEMENT TILE PER SPECS". THIS NOTE |
| | DOESN'T PROVIDE THE REQUIRED SPECIFIC |
| | INFORMATION. |
| | |
| | 7- PROVIDE SPECS FOR HOOD ABOVE BBQ |
| | GRILL APPROVED TO BE INSTALLED IN |
| | EXTERIOR LOCATION. INFORMATION SUBMITTED |
| | IS FOR INTERIOR INSTALLATION. |
| | |
| | 8- A) REVISE RIGHT ELEVATION TO MATCH. |
| | PLANS SHOW FRENCH DOORS, WHILE ELEVATION |
| | SHOW WINDOWS. |
| | B) SPECIFY DESIGN PRESSURES FOR ALL |
| | OPENINGS IN RIGHT ELEVATION. SEC. 1606 |
| | FBC 2001. |
| | |
| | 9- SPECIFY THE DESIGN PRESSURES FOR |
| | 9'X8' GARAGE DOOR. SEC. 1606 FBC 2001. |
| | |
| | 10- CHAPTER 481 FLORIDA STATUTE AND FAC |
| | SEC. 61G1-16.004: NEED NAME OF ARCHITECT |
| | SIGNING AND SEALING DRAWINGS IN ALL |
| | SHEETS. SOME SHEETS ARE MISSING THE |
| | ARCHITECT'S NAME AND ON THE OTHERS THE |
| | NAME OF THE ARCHITECT IS NOT LEGIBLE |
| | BECAUSE IS WRITTEN ON TOP OF THE BLACK |
| | BACKGROUND. SEE PLANS. REVISE AS REQ'D. |
| | |
| | 11- REVISE ENERGY CALCULATIONS: |
| | A) PLANS WERE APPROVED USING THE FBC |
| | 2001, NOT FBC 2004. REVISE FORM AS REQ'D |
| | B) A/C AREA TO MATCH REVISED AREA. |
| | C) REVISE UNDER ATTIC AREA. SEE SEC. |
| | 602.1ABC.1.2 OF CHAPTER 13 FBC 2001 TO |
| | INCLUDE THE AREAS CONSIDERED CEILING |
| | AREA. |
| | |
| | 12- PROVIDE COMPLETE INFORMATION FOR |
| | STAIRS: NEED DIMENSIONS, RISER AND |
| | TREADS SIZES. SEC.104.2.1.2 OF CITY |
| | AMENDMENTS TO FBC 2001 AND SECTION 1007 |
| | FBC 2001. |
| | |
| | 13- A) PROVIDE COMPLETE AND CLEAR SPECS |
| | AND DETAILS FOR ALL COLUMNS TO MATCH |
| | COLUMN LEGEND. EG: LANAI COLUMNS DON'T |
| | MATCH ONE SHOWN IN COLUMN LEGEND. |
| | B) COLUMN LEGEND: NUMBER OF RE-BARS |
| | SHOWN DON'T MATCH THE WRITTEN SPECS. SEE |
| | 8"X20" AND 12"X12" COLUMNS AND REVISE. |
| | |
| | 14- A) ROOF OVER CHIMNEY (ABOVE CHIMNEY |
| | FLUE): PROVIDE MANUFACTURER'S SPECS |
| | WHICH ALLOWS FLUE TERMINATION TO HAVE |
| | BUILT IN ROOF ABOVEAS SHOWN ON |
| | EXTERIOR ELEVATIONS. PROVIDE COMPLETE |
| | SPECS FOR CLEARANCES, MATERIALS, ETC. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC/01 |
| | B) CHIMNEY SHOWN ON REAR ELEVATION |
| | DOESN'T MATCH BUILDING SECTION SHOWN ON |
| | DRAWING A9. REVISE AS REQUIRED. |
| | |
| | 15- PROVIDE COMPLETE WALL SECTION THRU |
| | 2"X8" BEARING WALL ON 2ND FLOOR ABOVE |
| | GARAGE BY THE STAIRWAY. SPECIFY ALL |
| | FASTENERS. SECTION104.2.1.2 OF CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | 16- SHEET A9: |
| | A) SECTION 1 IS INCOMPLETE. |
| | B) CHIMNEY DETAIL: |
| | * SPECIFY ALL FASTENERS. |
| | **CHIMNEY DOESN'T MATCH ELEVATIONS. |
| | ***SPECIFY FIREBLOCKING MATERIAL |
| | & LOCATION. SEC. 2305.1 FBC 2001. |
| | **** RAILING DETAIL DOESN'T APPLY TO |
| | THIS PROJECT. REVISE AS REQUIRED. |
| | |
| | 17- TYPICAL 2 STORY WALL SECTION SHOWN |
| | ON SHEET A1 DOESN'T APPLY TO THIS |
| | PROJECT.REVISE AS REQUIRED. |
| | |
| | 18- SHEET A5: |
| | A) REVISE STRUCTURAL BUCK DETAILS. |
| | SEE SEC. 1707.4.4.2 FOR PROPER WAY OF |
| | INSTALLING BUCKS. BUCKS NEED TO PROVIDE |
| | FULL SUPPORT TO DOORS & WINDOWS FRAMES. |
| | B) SPECIFY SIZE OF STEEL PLATE FOR |
| | BOLLARD TO PROTECT GAS WATER HEATER. |
| | SEC. 104.1.2 CITY AMENDMENTS TO FBC 2001 |
| | |
| | 19- SHEET A7: |
| | A) CONNECTOR TH2 IS A WOOD TO WOOD |
| | CONNECTOR. NEED A WOOD TO MASONRY |
| | CONNECTOR. REVISE AS REQUIRED. SEE |
| | USP CATALOGUE FOR PROPER SELECTION. |
| | B) ROOF FRAMING PLAN BY LANAI AREA |
| | CALLS FOR 2TA8. THERE IS NOT TA8 |
| | CONNECTOR IN THE USP CATALOGUE. IS THERE |
| | A CUSTOM MADE CONNECTOR?. PROVIDE |
| | PRODUCT APPROVAL FOR IT. |
| | C) EMBEDDED MASONRY CONNECTOR SHOWN |
| | ON TOP RIGHT HAND SIDE CORNER: SPECIFY |
| | HOW LONG ARE THE #5 STUDS EMBEDDED INTO |
| | THE CONCRETE. SEC. 104.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (5610805-6712 |