| 2006-02-15 00:00:00 | BUILDING REVISION CHECKLIST: |
| | 1- INFORMATION REQUESTED ON PROVISO |
| | DATED 3-25-03 WAS NEVER SUBMITTED. |
| | CONTRACTOR AGREED TO PROVIDE INFORMATION |
| | BUT WAS NEVER SUBMITTED. PROVIDE ALL |
| | INFORMATION. SEE ATTACHED PROVISO COPY |
| | AND SUBMIT ALL INFORMATION. |
| | |
| | 2- SHEET A-5 NEED TO UPDATE AREA CALCS |
| | TO INCLUDE THE NEW A/C AREA AND REAR |
| | PORCH ADDITION. BRING PLANS TO PALM |
| | BEACH COUNTY TO UPDATE TOTAL SQUARE |
| | FOOTAGE AND PAY IMPACT FEES IF REQUIRED. |
| | BRING BACK STAMPED DRAWINGS. |
| | |
| | 3- PROVIDE PRODUCT APPROVAL FOR: |
| | A) OVAL WINDOW. |
| | B) 16'-0" X 9'-0" GARAGE DOOR. |
| | |
| | 4- PROVIDE CALCULATIONS FOR THE DESIGN |
| | PRESSURES CALCULATED FOR WINDOWS LOCATED |
| | AT THE END ZONE IN THE SECOND STORY |
| | BEDROOM ABOVE GARAGE. CALCULATIONS |
| | SUBMITTED ARE TOO LOW. REVISE AS |
| | REQUIRED. SEC. 104.2.1.2 OF CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | 5- ARCHITECT TO SPECIFY NUMBER AND TYPE |
| | OF NAILS REQUIRED FOR ROOF TILE |
| | FASTENING AS REQUIRED BY SEC. 104.2.1.1 |
| | OF CITY AMENDMENTS TO FBC 2001. |
| | |
| | 6- PROVIDE COMPLETE SPECS AND LISTING |
| | FOR "OUTDOOR" BBQ HOOD AND BBQ GRILL TO |
| | BE INSTALLED. SEC. 2808 FBC 2001. |
| | |
| | 7- RIGHT ELEVATION DOESN'T MATCH PLANS. |
| | SEE REVISED REAR PORCH. REVISE ELEVATION |
| | TO MATCH FLOOR PLANS. |
| | |
| | 8- ARCHITECT TO PROVIDE SPECIFIC DAY |
| | WHEN PLANS WERE SEALED. MONTH ALONE IS |
| | NOT A COMPLETE DATE. ALSO, PRINT THE |
| | NAME OF THE PERSON SEALING THE PLANS. |
| | SEE CHAPTER 481 FLORIDA STATUTES AND |
| | 61G1-16.004 OF FLORIDA ADMINISTRATIVE |
| | CODE FOR TITLE BLOCK REQUIREMENTS. |
| | PROVIDE COMPLETE INFORMATION AS REQ'D. |
| | |
| | 9- PROVIDE REVISED ENERGY CALCULATIONS |
| | SHOWING NEW A/C AREA. |
| | |
| | 10- PROVIDE COMPLETE INFORMATION FOR |
| | STAIR:SECTION/DETAIL TRHU STAIRS. |
| | SPECIFY RAILING HEIGHT AND LOCATION. |
| | RISER AND TREAD DIMENSIONS. STAIR WIDTH. |
| | SEC. 1007 FBC 2001. |
| | |
| | 11- PROVIDE COMPLETE SPECS AND DETAILS |
| | FOR ALL COLUMNS AT COVERED LANAI. |
| | INCLUDING COLUMN BY BBQ AREA. SPECIFY |
| | TOP AND BOTTOM CONNECTIONS. SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | |
| | 12- PROVIDE COMPLETE BATHROOM WITH DOOR |
| | THAT ALLOWS 29"CLEAR OPENING AS REQUIRED |
| | BY SEC. 11-11 FBC 2001. |
| | |
| | 13- SPECIFY ATTIC ACCESS IN SECOND FLOOR |
| | AS REQUIRED BY SEC. 2309.6 FBC 2001. |
| | |
| | 14- PROVIDE COMPLETE DETAIL/SECTION WITH |
| | SPECS FOR ATTACHMENT OF WOOD BUCKS TO |
| | STEEL COLUMNS AT LIVING ROOM AREA. |
| | (NOTE: TAPCONS ARE MASONRY CONNECTORS. |
| | NOT DESIGNED FOR WOOD OR STEEL). |
| | |
| | 15- CHIMNEY FLUE CAP. PROVIDE |
| | MANUFATURER'S INFORMATION WHICH ALLOWS |
| | FLUE TERMINATION TO HAVE BUILT IN FLUE |
| | CAP AS SHOWN ON EXTERIOR ELEVATIONS. |
| | PROVIDE COMPLETE SPECS FOR CLEARANCES, |
| | MATERIALS, ETC. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | 16- SECOND FLOOR PLAN IS MISSING |
| | INFORMATION. NEED DIMENSIONS, ROOM |
| | NAMES, DOOR SIZES. WINDOW TYPE AND SIZES |
| | TO VERIFY EGRESS REQUIREMENTS. |
| | |
| | 17- PROVIDE COMPLETE WALL SECTION THRU |
| | 2X8 BEARING WALL ON SECOND FLOOR ABOVE |
| | GARAGE BY THE STAIRWAY. SPECIFY ALL |
| | FASTENERS. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | 18- SECOND FLOOR ROOF FRAMING PLAN. |
| | SPECIFY ALL TRUSS CONNECTIONS AT MASONRY |
| | AND AT WOOD FRAMED WALL. SEC. 104.2.1.2 |
| | CITY AMENDMENTS TO FBC 2001. |
| | |
| | 19- NEED TO SPECIFY SMOKE DETECTORS AT |
| | FIRST FLOOR AND SECOND FLOOR AS REQUIRED |
| | BY SEC. 905.2.2 FBC 2001. |
| | |
| | 20- NEED RE-RECORDED NOC. NOC EXPIRES 1 |
| | YR AFTER RECORDING. |
| | |
| | 21- SHEET A4: A) REVISE SPACING FOR WWM |
| | SUPPORTS. SEE SEC. 1909.3 FBC 2001. |
| | B) SPECIFY COLUMN SIZE & REINFORCEMENT |
| | FOR COLUMN AT ENTRY PORCH, LIVING ROOM, |
| | BEDROOM #4 VESTIBULE. SEE PLANS FOR |
| | COMMENTS. |
| | C) SPECIFY FOOTING PAD FOR STEEL |
| | COLUMNBY GARAGE STAIRWAY. |
| | |
| | 22- SHEET A5: A) WHERE ARE SECTIONS 1/A2 |
| | AND 2/A2 LOCATED AT?. |
| | B) PROVIDE COMPLETE SPECS/DETAILS FOR |
| | BOLLARD TO PROTECT GAS WATER HEATER. |
| | SPECIFY EMBEDMENT, REINFORCEMENT, ETC. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC/01 |
| | |
| | 23- SHEET A7: A) SPECIFY BEAM AT LANAI |
| | AREA BY THE LIVING AREA. SEE COMMENTS ON |
| | PLANS. |
| | B) WHAT'S CONNECTOR TH2 AND BU |
| | SPECIFIED AT SECOND FLOOR FRAMING PLAN |
| | BY THE GARAGE AREA? |
| | C) SHOW CRICKET AT CUPOLA ABOVE MASTER |
| | BATHROOM. SEE PLANS. |
| | D) SPECIFY ALL CONNECTORS.SEE PLANS |
| | FOR MISSING CONNECTORS. SEC. 104.2.1.2 |
| | CITY AMENDMENTS TO FBC 2001. |
| | |
| | ***NOTE: RETURN REDLINED PRINTS AFTER |
| | CORRECTIONS ARE DONE TO ORIGINAL |
| | DRAWINGS TO EXPEDITE REVIEW PROCESS. |
| | |
| | 24- SHEET A9: A) SECTION1 DOESN'T |
| | MATCH PLANS. REVISE AS REQUIRED. |
| | B) CHIMNEY DETAIL: SPECIFY ALL |
| | FASTENERS. SEE COMMENTS ON PLANS. ALSO, |
| | SPECS CALL FOR VERTICAL FRAMING TO |
| | EXTEND INTO ATTIC AND TO BE ATTACHED TO |
| | TRUSS BOTTOM CHORD. REVISE DETAIL TO |
| | REFLECT THESE SPECIFICATIONS. SEE PLANS. |
| | |
| | C) WHERE IS SECTION SHOWN AT BOTTOM OF |
| | PAGE TAKEN AT? SEE PLANS. ALSO, UPDATE |
| | CONNECTOR. |
| | D) TYP. 1 STORY WALL SECTION: UPDATE |
| | HUGHES CONNECTOR AND SPECIFY SIZE AND |
| | NUMBER OF NAILS TO HOLD ROOF TILE. |
| | |
| | 25- PROVIDE COMPLETE 2 STORY WALL |
| | SECTION. SEC. 104.2.1.2 CITY AMENDMENTS |
| | TO FBC 2001. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |