Plan Review Notes
Plan Review Notes For Permit 02111519
Permit Number 02111519
Review Stop R
Sequence Number 4
Notes
Date Text
2006-02-15 00:00:00BUILDING REVISION CHECKLIST:
 1- INFORMATION REQUESTED ON PROVISO
 DATED 3-25-03 WAS NEVER SUBMITTED.
 CONTRACTOR AGREED TO PROVIDE INFORMATION
 BUT WAS NEVER SUBMITTED. PROVIDE ALL
 INFORMATION. SEE ATTACHED PROVISO COPY
 AND SUBMIT ALL INFORMATION.
  
 2- SHEET A-5 NEED TO UPDATE AREA CALCS
 TO INCLUDE THE NEW A/C AREA AND REAR
 PORCH ADDITION. BRING PLANS TO PALM
 BEACH COUNTY TO UPDATE TOTAL SQUARE
 FOOTAGE AND PAY IMPACT FEES IF REQUIRED.
 BRING BACK STAMPED DRAWINGS.
  
 3- PROVIDE PRODUCT APPROVAL FOR:
 A) OVAL WINDOW.
 B) 16'-0" X 9'-0" GARAGE DOOR.
  
 4- PROVIDE CALCULATIONS FOR THE DESIGN
 PRESSURES CALCULATED FOR WINDOWS LOCATED
 AT THE END ZONE IN THE SECOND STORY
 BEDROOM ABOVE GARAGE. CALCULATIONS
 SUBMITTED ARE TOO LOW. REVISE AS
 REQUIRED. SEC. 104.2.1.2 OF CITY
 AMENDMENTS TO FBC 2001.
  
 5- ARCHITECT TO SPECIFY NUMBER AND TYPE
 OF NAILS REQUIRED FOR ROOF TILE
 FASTENING AS REQUIRED BY SEC. 104.2.1.1
 OF CITY AMENDMENTS TO FBC 2001.
  
 6- PROVIDE COMPLETE SPECS AND LISTING
 FOR "OUTDOOR" BBQ HOOD AND BBQ GRILL TO
 BE INSTALLED. SEC. 2808 FBC 2001.
  
 7- RIGHT ELEVATION DOESN'T MATCH PLANS.
 SEE REVISED REAR PORCH. REVISE ELEVATION
 TO MATCH FLOOR PLANS.
  
 8- ARCHITECT TO PROVIDE SPECIFIC DAY
 WHEN PLANS WERE SEALED. MONTH ALONE IS
 NOT A COMPLETE DATE. ALSO, PRINT THE
 NAME OF THE PERSON SEALING THE PLANS.
 SEE CHAPTER 481 FLORIDA STATUTES AND
 61G1-16.004 OF FLORIDA ADMINISTRATIVE
 CODE FOR TITLE BLOCK REQUIREMENTS.
 PROVIDE COMPLETE INFORMATION AS REQ'D.
  
 9- PROVIDE REVISED ENERGY CALCULATIONS
 SHOWING NEW A/C AREA.
  
 10- PROVIDE COMPLETE INFORMATION FOR
 STAIR:SECTION/DETAIL TRHU STAIRS.
 SPECIFY RAILING HEIGHT AND LOCATION.
 RISER AND TREAD DIMENSIONS. STAIR WIDTH.
 SEC. 1007 FBC 2001.
  
 11- PROVIDE COMPLETE SPECS AND DETAILS
 FOR ALL COLUMNS AT COVERED LANAI.
 INCLUDING COLUMN BY BBQ AREA. SPECIFY
 TOP AND BOTTOM CONNECTIONS. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 12- PROVIDE COMPLETE BATHROOM WITH DOOR
 THAT ALLOWS 29"CLEAR OPENING AS REQUIRED
 BY SEC. 11-11 FBC 2001.
  
 13- SPECIFY ATTIC ACCESS IN SECOND FLOOR
 AS REQUIRED BY SEC. 2309.6 FBC 2001.
  
 14- PROVIDE COMPLETE DETAIL/SECTION WITH
 SPECS FOR ATTACHMENT OF WOOD BUCKS TO
 STEEL COLUMNS AT LIVING ROOM AREA.
 (NOTE: TAPCONS ARE MASONRY CONNECTORS.
 NOT DESIGNED FOR WOOD OR STEEL).
  
 15- CHIMNEY FLUE CAP. PROVIDE
 MANUFATURER'S INFORMATION WHICH ALLOWS
 FLUE TERMINATION TO HAVE BUILT IN FLUE
 CAP AS SHOWN ON EXTERIOR ELEVATIONS.
 PROVIDE COMPLETE SPECS FOR CLEARANCES,
 MATERIALS, ETC. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 16- SECOND FLOOR PLAN IS MISSING
 INFORMATION. NEED DIMENSIONS, ROOM
 NAMES, DOOR SIZES. WINDOW TYPE AND SIZES
 TO VERIFY EGRESS REQUIREMENTS.
  
 17- PROVIDE COMPLETE WALL SECTION THRU
 2X8 BEARING WALL ON SECOND FLOOR ABOVE
 GARAGE BY THE STAIRWAY. SPECIFY ALL
 FASTENERS. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 18- SECOND FLOOR ROOF FRAMING PLAN.
 SPECIFY ALL TRUSS CONNECTIONS AT MASONRY
 AND AT WOOD FRAMED WALL. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
  
 19- NEED TO SPECIFY SMOKE DETECTORS AT
 FIRST FLOOR AND SECOND FLOOR AS REQUIRED
 BY SEC. 905.2.2 FBC 2001.
  
 20- NEED RE-RECORDED NOC. NOC EXPIRES 1
 YR AFTER RECORDING.
  
 21- SHEET A4: A) REVISE SPACING FOR WWM
 SUPPORTS. SEE SEC. 1909.3 FBC 2001.
 B) SPECIFY COLUMN SIZE & REINFORCEMENT
 FOR COLUMN AT ENTRY PORCH, LIVING ROOM,
 BEDROOM #4 VESTIBULE. SEE PLANS FOR
 COMMENTS.
 C) SPECIFY FOOTING PAD FOR STEEL
 COLUMNBY GARAGE STAIRWAY.
  
 22- SHEET A5: A) WHERE ARE SECTIONS 1/A2
 AND 2/A2 LOCATED AT?.
 B) PROVIDE COMPLETE SPECS/DETAILS FOR
 BOLLARD TO PROTECT GAS WATER HEATER.
 SPECIFY EMBEDMENT, REINFORCEMENT, ETC.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC/01
  
 23- SHEET A7: A) SPECIFY BEAM AT LANAI
 AREA BY THE LIVING AREA. SEE COMMENTS ON
 PLANS.
 B) WHAT'S CONNECTOR TH2 AND BU
 SPECIFIED AT SECOND FLOOR FRAMING PLAN
 BY THE GARAGE AREA?
 C) SHOW CRICKET AT CUPOLA ABOVE MASTER
 BATHROOM. SEE PLANS.
 D) SPECIFY ALL CONNECTORS.SEE PLANS
 FOR MISSING CONNECTORS. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
  
 ***NOTE: RETURN REDLINED PRINTS AFTER
 CORRECTIONS ARE DONE TO ORIGINAL
 DRAWINGS TO EXPEDITE REVIEW PROCESS.
  
 24- SHEET A9: A) SECTION1 DOESN'T
 MATCH PLANS. REVISE AS REQUIRED.
 B) CHIMNEY DETAIL: SPECIFY ALL
 FASTENERS. SEE COMMENTS ON PLANS. ALSO,
 SPECS CALL FOR VERTICAL FRAMING TO
 EXTEND INTO ATTIC AND TO BE ATTACHED TO
 TRUSS BOTTOM CHORD. REVISE DETAIL TO
 REFLECT THESE SPECIFICATIONS. SEE PLANS.
  
 C) WHERE IS SECTION SHOWN AT BOTTOM OF
 PAGE TAKEN AT? SEE PLANS. ALSO, UPDATE
 CONNECTOR.
 D) TYP. 1 STORY WALL SECTION: UPDATE
 HUGHES CONNECTOR AND SPECIFY SIZE AND
 NUMBER OF NAILS TO HOLD ROOF TILE.
  
 25- PROVIDE COMPLETE 2 STORY WALL
 SECTION. SEC. 104.2.1.2 CITY AMENDMENTS
 TO FBC 2001.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712.