| Plan Review Notes For Permit 02111519 |
| Permit Number |
02111519 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-03-03 00:00:00 | *** DENIED *** | | | 1) ENERGY CALCULATIONS ARE CALLING FOR | | | 113,600 TOTAL BTU'S, AND THE PLANS ARE | | | CALLING FOR 119,900 TOTAL BTU'S. THE | | | PLANS CAN NOT CALL FOR MORE BTU'S THAN | | | THE E-CAL'S, PLEASE CORRECT. | | | | | | 2) AHU #1 SUPPLT AIR DUCT TO FIRST FLOOR | | | IS 12" SO THE RETURN AIR DUCT NEEDS TO | | | BE 12" NOT 10" PLEASE CORRECT. | | | | | | 3) AHU #1 THE RETURN AIR DUCT TO THE | | | SECOND FLOOR NEEDS TO BE SIZED. | | | | | | 4) THE RETURN AIR GRILL 30X18 TO AHU #2 | | | IS TO SMALLFOR A 5 TON SYSTEM PLEASE | | | CORRECT. | | | | | | 5) NOT ALL SUPPLY AIR DUCTS ARE SIZED | | | PLEASE CHECK AND CORRECT. | | | | | | 6) THE JOB ADDERSS MUST APPEAR ON ALL | | | SHEETS OF THE PLANS. | | | | | | 7)ALL INFORMATION, DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA | | | SHALL BEAR THE NAME AND SIGNATURE OF THE | | | PERSON RESPONSIBLE FOR THE DESIGN. PER | | | FBC 104.2.1 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. | | | |
|