| 2003-03-25 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: |
| | 1-WIND LOAD CRITERIA: CLEARLY LIST ALL |
| | FIVE ITEMS AS REQUIRED BY SECTION |
| | 1606.1.7 FBC 2001. |
| | 2-REVISE EXTERIOR ELEVATIONS TO MATCH |
| | FLOOR PLANS. SEE FLOOR PLAN AND ROOF |
| | FRAMING PLAN AND REVISE AS REQUIRED. |
| | 3-NEED COMPLETE INFORMATION ON CHIMNEY |
| | FRAMING SECTION AND CUPOLAS FRAMING |
| | PLANS. CLEARLY SPECIFY ALL FASTENERS. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | 4-NEED COMPLETE INFORMATION ON DETAIL AT |
| | CONNECTION OF WINDOWS TO STEEL COLUMNS |
| | CLEARLY SPECIFY ALL FASTENERS. SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 5-SPECIFY WWM SUPPORTS AND SPACING ON |
| | CONCRETE SLAB. SEE SECTION 1909.3 |
| | FBC 2001. |
| | 6-REVISE STRUCTURAL BUCK DETAIL FOR |
| | SWING DOORS. SEE SEC. 1707.4.4.2 FBC. |
| | 7-SEE PLANS FOR ADDITIONAL COMMENTS AND |
| | PROVIDE INFORMATION/CLARIFICATION. |
| | 8-PROVIDE PRODUCT APPROVAL FOR ENTRY |
| | DOOR W/ TRANSOM ABOVE SINGLE ASSEMBLY, |
| | FRENCH DOORS WITH TRANSOM ABOVE SINGLE |
| | ASSEMBLY OR ARCHITECT TO DESIGN THE |
| | STRUCTURAL HEADER TO BE PART OF BLDG |
| | STRUCTURE. SEC. 104.2.1.2 CITY AMEND- |
| | MENTS TO FBC 2001. |
| | 9-PROVIDE FIREPLACE AND BBQ UL LISTING |
| | AND COMPLETE SPECS. |
| | 10-PROVIDE COMPLETE PRODUCT APPROVAL FOR |
| | GARAGE DOORS. INCLUDING COMPLETE |
| | PRODUCT APPROVAL REPORT AND DRAWINGS. |
| | 11-PROVIDE SOIL TEST REPORT. |