| Plan Review Notes For Permit 02111490 |
| Permit Number |
02111490 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2003-05-29 00:00:00 | PROVISO | | | ~~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE NOTE THAT THE ADDED RECEPTACLES | | | WERE NOT ADDED TO THE TOTAL IN THE LOAD | | | CALC'S PER 220-3(B)(9).ALTHOUGH THIS IS | | | A SMALL AMPERAGE AMOUNT,PLEASE | | | KEEP ALL CHANGES CURRENT.PLEASE MAKE | | | THIS CORRECTION ON THE NEXT REVISION. | | | | | | ALSO THE SIGN LIGHTING CIRCUIT MUST BE | | | CHANGED TO COMPLY WITH 600-5(B)(3),1200 | | | VA. | | | | | | PLEASE NOTE THAT THE PROVISO FROM THE | | | LAST REVIEW WAS NOT ADDRESSED.INCLUDE | | | THOSE REVISIONS WITH THE NEXT SUBMITTAL. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 5691/805-6718 |
|