Plan Review Notes
Plan Review Notes For Permit 02111490
Permit Number 02111490
Review Stop P
Sequence Number 3
Notes
Date Text
2003-03-20 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FBC-2001 FUEL GAS
  
 1) RODNEY COMPO, ENVIRONMENTAL COMPLI-
 ANCE HAS NOT BEEN CONTACTED AS OF YET.
 I CALLED HIM AND THE CONTRACTOR AND THEY
 WILL INFORM ME AS TO THE SIZE OF GREASE
 TRAP THAT WILL BE REQUIRED.
 2) ROOF DRAIN/SCUPPER FOR 1803 SQ FT -
 1985 SQ FT COMBINATION IS NOT SUFFICIENT
 FOR THIS AREA. MINIMUM OF 113 SQ IN
 OPENING IS REQUIRED FOR THIS ROOF DRAIN/
 SCUPPER COMBINATION OPENING.
 3) RECOMMENDED LAV HEIGHT FOR CHILDREN
 AGES 2 THRU 5 IS 20" TO 24". SEE ATTACH-
 ED SHEET.
 4) GAS PERMIT WILL BE SEPARATE. INFOR-
 MATION REQUIRED AT TIME OF APPLICATION,
 TYPE OF GAS, - DELIVERY PRESSURE, - AND
 MANUFACTURE SHEETS FOR GAS RANGE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377