Plan Review Notes
Plan Review Notes For Permit 02111490
Permit Number 02111490
Review Stop E
Sequence Number 3
Notes
Date Text
2003-02-27 00:00:00*************** NOTES REDLINED ******
  
 REVISE WITH ANY OTHER CHANGES BEFORE
 ROUGH ELECTRICAL INSPECTION IS CALLED IN
  
  
 1)NOTE: PLEASE SEE OCP SHOWN FOR PANEL
 "K". SHOWS 200A FUSE ON # 1/0`S,
 PLEASE CORRELATE PER 240-3,310-16
  
 2)NOTE: PLEASE SEE RISER DIAGRAM, SHOWS
 AN EQUIPMENT GROUND BETWEEN METER AND
 MAIN DISC'S. EQUIPMENT GROUNDING CONDUCT
 -OR IS ONLY INSTALLED AFTER FIRST MEANS
 OF DISC. 250-24
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE ROUGH. IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  