Plan Review Notes
Plan Review Notes For Permit 02111490
Permit Number 02111490
Review Stop M
Sequence Number 2
Notes
Date Text
2003-02-13 00:00:00PROVISO:
  
 ACCESS FOR RTU 5 & 6 SHALL NOT REQUIRE
 CLIMBING OVER OBSTRUCTIONS GREATER THAN
 30" (2001 FBC(M) 306.5).
  
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRE SUPRESSION AND WALK-IN COOLERS.
 PLEASE PROVIDE PLANS & MANUFACTURERS
 SUBMITTAL DATA WITH PERMIT APPLICATION.
 PLAN SHEET M-1 NOTE #13 INDICATES GREASE
 DUCT TO BE WRAPPED WITH FIRE WRAP.
 PROVIDE SUBMITTAL FOR THE FIRE WRAP
 WITH HOOD PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.