| Plan Review Notes For Permit 02111490 |
| Permit Number |
02111490 |
|
| Review Stop |
ENG |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-01-28 00:00:00 | FAILED: | | | 1. IN ADDITION TO PREVIOUS REVIEW | | | COMMENTS DATED 01/16/03 (SEE ATTACHED) | | | ITEMS BELOW MUST BE ADDRESSED, | | | 1. PLEASE DISRGARD COMMENT NO. 6 OF THE | | | PREVIOUS REVIEW. | | | 2. DRAINAGE CALCULATIONS SHOWS INVERT | | | ELEVATION FOR V-NOTCH AT 17.71, DETAIL | | | ON SHEET C-1 OF 3 SHOWS 18.21 PLEASE | | | VERIFY. | | | 3. SIDEWALK ALONG THE PROPERTY ON | | | SOUTHERN BLVD. MUST BE RESTORED AND MUST | | | BE ACCESSIBLE, CURB CUT RAMPS MUST BE | | | INSTALLED AT PROPOSED ENTRANCES. | | | 4. PLEASE NOTE THAT A SEPARATE PERMIT | | | FROM FDOT FOR WORK WHITEN SOUTHERN BLVD. | | | ROW WILL BE REQUIRED. | | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | | EXT. 8492 MOHAMMAD R. AMINI |
|