| Date |
Text |
| 2002-12-26 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1) PLEASE ROUTE PLANS TO PALM BEACH |
| | COUNTY HEALTH UNIT, DIVISION OF ENVIRON- |
| | MENTAL HEALTH, 901 EVERNIA ST W.P.B |
| | (561) 355-3018.SECTION 101.4.7 |
| | 2) CONTACT RODNEY COMPO, ENVIRONMENTAL |
| | COMPLIANCE, FOR GREASE TRAP REQUIREMENTS |
| | WASTE ORD. #2938-96 (561) 837-4074 |
| | 3) SHT D-1, NOTE G - DEMO PERMIT REQUIR- |
| | ED FOR PLUMBING. |
| | 4) SHT A1.1 ROOM 104, DOOR SHALL NOT |
| | OPEN INTO THE CLEAR FLOOR SPACE OF LAV. |
| | 5) PLEASE INDICATE CLEAR FLOOR SPACE FOR |
| | ALL HDCP FIXTURES, AND SHOW 5' TURNING |
| | RADIUS FOR EACH TOILET ROOM. |
| | 6) SHT A1.3, PLEASE PROVIDE CALCULATIONS |
| | FOR THE PRIMARY & SECONDARY ROOF DRAINS, |
| | PER SECTIONS 1106 & 1107. INCLUDE 1/2 |
| | AREA OF ALL VERTICAL WALLS. ALSO SHOW |
| | LOCATION OF ALL SECONDARY ROOF DRAINS. |
| | 7) SHT A5.1, SCUPPER DETAIL, PLEASE IN- |
| | DICATE TOTAL AREA OF SCUPPER OPENING. |
| | THE ONLY DIMENSION SHOWN IS 4" HIGH. |
| | 8) SHT A6.2, ROOM 115 DETAIL, SINK IN |
| | LOUNGE SHALL COMPLY WITH 4.24 AND ALL |
| | SUBSECTIONS. PLEASE SHOW ON DETAIL. |
| | 9) SHTS FS-3 & P-3 ALL INDIRECT WASTE |
| | SHALL DRAIN INTO A FLOOR SINK. SECTION |
| | 802.3. FUNNEL FLOOR DRAIN ON GREASE |
| | SYSTEM NOT APPROVED. |
| | 10) SHT P-2, GREASE TRAP DETAIL, PLEASE |
| | SEE ATTACHED SHEET FOR APPROVED CITY OF |
| | WEST PALM BEACH STANDARD GREASE TRAP DE- |
| | TAIL. |
| | 11) SHT P-3, STORM DRAIN ISOMETRIC, SIZE |
| | OF STORM DRAINAGE PIPING REQUIRED FOR |
| | BLDG. DRAIN. |
| | 12) SHT P-4, WATER ISOMETRIC, AIR CHAMB- |
| | ERS ARE NOT APPROVED, PLEASE DELETE FROM |
| | ISO. ALL WATER HAMMER ARRESTORS REQUIRED |
| | BY 604.9 SHALL BE LOCATED NEAR THE FIX- |
| | TURES IN AN "EFFECTIVE RANGE" NOT IN |
| | CEILING AT TOP OF DROP. |
| | 13) WILL THE FIXTURES FOR CHILDREN BE |
| | LOWERED PER ADA GUIDELINES FOR BUILDINGS |
| | & FACILITIES; BUILDING ELEMENTS DESIGNED |
| | FOR CHILDREN'S USE? |
| | 14) FOLLOWING INFORMATION REQUIRED FOR |
| | APPLICATION FOR GAS (SEPARATE) PERMIT. |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | SPECIFICATION BOOK SHOWS "A" COPPER |
| | TUBING & "B" SCHED. 40 STEEL PIPE. |
| | PLEASE CLAIRFY. |
| | C. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). |
| | D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2 |
| | E. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. - UNION NOT |
| | SHOWN ON PLANS. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |