2002-12-23 00:00:00HVAC NOTES:
 PLAN SHEET M-1 PRESCHOOL RM 129, PLAN
 INDICATES A FIRE DAMPER AT OVER THE DOOR
 TO THIS ROOM.ARCHITECTURAL PLAN DOES
 NOT INDICATE THIS AS A RATED WALL.
 PLEASE CLARIFY.
  
 AS PER 2001 FBC(M) 306.5 EQUIPMENT
 LOCATED ON ROOFS OR ELEVATED STRUCTURES,
 ACCESS TO RTU'S #1, 2, 5 & 6 SHALL NOT
 REQUIRE CLIMBING OVER OBSTRUCTIONS
 GREATER THAN 30".
  
 PROVIDE INFORMATION ON THE ROOF RACK FOR
 THE CONDENSING UNITS FOR THE WALK-IN
 COOLER/FREEZER.SHOW COMPLIANCE WITH
 2001 FBC TABLE 1511.7 FOR THE STAND
 CLEARANCE BETWEEN FINISHED ROOF & THE
 BOTTOM OF THE SUPPORT RAIL.
  
 HOOD PLAN REVIEW:
 ADDITIONAL PERMIT REQUIRED FOR HOOD.
 PLAN SHEET M-1 DRAWING KEYNOTE #13,
 INDICATES THE GREASE DUCT IN A 2 HR
 SHAFT.PLEASE PROVIDE CROSS-SECTION
 DETAIL OF UL RATED ASSEMBLY.INSPECTION
 OF WELDS REQUIRED PRIOR TO COVERING
 DUCTWORK.
  
 EXHAUST TERMINATION SHALL BE LOCATED NOT
 LESS THAN 10 FT HORIZONTALLY FROM PARTS
 OF THE SAME OR CONTIGUOUS BUILDINGS,
 ADJACENT PROPERTY LINES & AIR INTAKE
 OPENINGS.2001 FBC(M) 506.3.14.3.
  
 WALK-IN COOLER & FREEZER:
 PROVIDE MANUFACTURER SUBMITTAL DATA &
 INSTALLATION INSTRUCTIONS WITH PERMIT
 APPLICATION.
  
 ADDITIONAL PERMIT REQUIRED FOR FIRE
 SUPRESSION.PLEASE PROVIDE PLANS WITH
 PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.