| Date |
Text |
| 2002-12-23 00:00:00 | HVAC NOTES: |
| | PLAN SHEET M-1 PRESCHOOL RM 129, PLAN |
| | INDICATES A FIRE DAMPER AT OVER THE DOOR |
| | TO THIS ROOM.ARCHITECTURAL PLAN DOES |
| | NOT INDICATE THIS AS A RATED WALL. |
| | PLEASE CLARIFY. |
| | |
| | AS PER 2001 FBC(M) 306.5 EQUIPMENT |
| | LOCATED ON ROOFS OR ELEVATED STRUCTURES, |
| | ACCESS TO RTU'S #1, 2, 5 & 6 SHALL NOT |
| | REQUIRE CLIMBING OVER OBSTRUCTIONS |
| | GREATER THAN 30". |
| | |
| | PROVIDE INFORMATION ON THE ROOF RACK FOR |
| | THE CONDENSING UNITS FOR THE WALK-IN |
| | COOLER/FREEZER.SHOW COMPLIANCE WITH |
| | 2001 FBC TABLE 1511.7 FOR THE STAND |
| | CLEARANCE BETWEEN FINISHED ROOF & THE |
| | BOTTOM OF THE SUPPORT RAIL. |
| | |
| | HOOD PLAN REVIEW: |
| | ADDITIONAL PERMIT REQUIRED FOR HOOD. |
| | PLAN SHEET M-1 DRAWING KEYNOTE #13, |
| | INDICATES THE GREASE DUCT IN A 2 HR |
| | SHAFT.PLEASE PROVIDE CROSS-SECTION |
| | DETAIL OF UL RATED ASSEMBLY.INSPECTION |
| | OF WELDS REQUIRED PRIOR TO COVERING |
| | DUCTWORK. |
| | |
| | EXHAUST TERMINATION SHALL BE LOCATED NOT |
| | LESS THAN 10 FT HORIZONTALLY FROM PARTS |
| | OF THE SAME OR CONTIGUOUS BUILDINGS, |
| | ADJACENT PROPERTY LINES & AIR INTAKE |
| | OPENINGS.2001 FBC(M) 506.3.14.3. |
| | |
| | WALK-IN COOLER & FREEZER: |
| | PROVIDE MANUFACTURER SUBMITTAL DATA & |
| | INSTALLATION INSTRUCTIONS WITH PERMIT |
| | APPLICATION. |
| | |
| | ADDITIONAL PERMIT REQUIRED FOR FIRE |
| | SUPRESSION.PLEASE PROVIDE PLANS WITH |
| | PERMIT APPLICATION. |
| | |