| Date |
Text |
| 2003-01-16 00:00:00 | FAILED : |
| | 1. PLEASE NOTE THAT A SEPARATE PERMIT |
| | APPLICATION AND FEES FOR UNDERGROUND |
| | UTILITIES AND CIVIL SITE WORK WILL BE |
| | REQUIRED. |
| | 2. ALL THE NEW CONNECTIONS TO CITY |
| | SERVICES, BACKFLOW PREVENTERS AND |
| | LOCATIONS MUST BE APPROVED BY PUBLIC |
| | UTILITIES ENGINEERING SERVICES, PLEASE |
| | SUBMIT PLANS AND CALCULATIONS FOR STORM- |
| | WATER, SEWER AND DOMESTIC WATER. |
| | MR. MANNY GONZALEZ 659-8040 EXT. 2306 |
| | 3. PLEASE CONTACT MR. RODNEY COMPO |
| | FOR INSTALLATION, SIZE, LOCATION OF THE |
| | PROPOSED GREASE/WATER. 837-4051 EXT. |
| | 4074 |
| | 4. DRIVEWAY APPROACHES AS SHOWN DO NOT |
| | MATCH THE SANDARD SHOWN ON SHEET C-3 OF |
| | 3, DRIVEWAY APPROACHES MUST AT MIN. BE |
| | PER CITY STANDARD. |
| | 5. INDEXES MUST BE INCLUDED ON SHEET C-3 |
| | OF 3, IF THEY ARE REFERED TO. SEE SHEET |
| | C-2 OF 3. |
| | 6. IF MANHOLE #3 IS A CONTROL STRUCTURE |
| | THEN DETAILS MUST BE SHOWN. |
| | 7. SHEET C-2 OF 3 REFERS TO PER CITY OF |
| | WPB STANDARD G-5 FOR CONNECTION OF SEWER |
| | LATERAL, PLEASE VERIFY. |
| | 8. PLEASE SHOW ELEVATIONS ON EXFILTRA- |
| | TION TRANCH DETAILS. |
| | IF ANY QUESTIONS PLEASE CONTACT 659-8096 |
| | EXT. 8492 MOHAMMAD R. AMINI |