2002-12-04 00:00:00************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE, CIRCUITING ON
 PLANS AND PANELS NEED TO CORRELATE.
 PLEASE NOTE THERE ARE MANY CIRCUITS ON
 PLANS THAT REPEAT. PLEASE NOTE, THERE
 ARE ALSO MISSING CIRCUIT(S).
  
 2)NOTE: PLEASE NOTE, LOADS ON CIRCUITS
 NEED TO BE VERIFIED. SOME DO NOT SEEM TO
 MATCH UP W/ # OF RECEPTS @ 180VA PER
 RECEPT.220-13.
  
 3)NOTE: PLEASE PROVIDE NOTE ON PLANS
 FOR HOOD SHUT DOWN PER NFPA-96 7-3.1.3.1
  
 4)NOTE: PLEASE CLARIFY TYPE OF FIXTURES
 TO BE USED IN HOODS ON FIXTURE SCHEDULE
 PER 410-4 AND NFPA-96 7-3
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  