Plan Review Notes
Plan Review Notes For Permit 02111490
Permit Number 02111490
Review Stop B
Sequence Number 1
Notes
Date Text
2003-01-16 00:00:00THE PRINCIPAL USE OF THIS BUILDING IS IN
 OCCUPANCY GROUP E AS FOUND IN FBC 313.1
  
 THE CORRIDOR SHOWN AS #138 ON SHEET
 A1.1 IS REQUIRED BY FBC TABLE 704.2.4,
 NOTE 4 TO BE CONSTRUCTED TO RESIST THE
 PASSAGE OF SMOKE.THE PARTITION TYPE
 SHOWN AS A3 ON SHEET A5.4 DOES NOT
 COMPLY.PLEASE REVISE AS NECESSARY.
  
 FBC TABLE 1004 REQUIRES A MININMUM 72"
 WIDE CORRIDOR FOR GROUP E OCCUPANCIES.
 CORRIDOR #138 DOES NOT COMPLY.
  
 THE PLANS AND SPECIFICATIONS DO NOT
 DECLARE THE METHOD OF HURRICANE MISSILE
 IMPACT RESISTANCE IN ACCORDANCE WITH
 FBC 1606.1.4.
  
 IF TEST AND OR NOTICE OF ACCEPTANCE
 REPORTS FOR THE EXTERIOR DOORS, WINDOWS
 AND ROOF COVERINGS ARENOT INCLUDED
 WITH THIS PERMIT APPLICATION, A
 SEPARATE PERMIT AND ADDITIONAL FEES
 WILL BE REQUIRED.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, THE PERMIT PLANS STAMPED
 BY THAT OFFICE AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 561-233-5025 FOR
 MORE INFORMATION.