| Date |
Text |
| 2003-01-16 00:00:00 | THE PRINCIPAL USE OF THIS BUILDING IS IN |
| | OCCUPANCY GROUP E AS FOUND IN FBC 313.1 |
| | |
| | THE CORRIDOR SHOWN AS #138 ON SHEET |
| | A1.1 IS REQUIRED BY FBC TABLE 704.2.4, |
| | NOTE 4 TO BE CONSTRUCTED TO RESIST THE |
| | PASSAGE OF SMOKE.THE PARTITION TYPE |
| | SHOWN AS A3 ON SHEET A5.4 DOES NOT |
| | COMPLY.PLEASE REVISE AS NECESSARY. |
| | |
| | FBC TABLE 1004 REQUIRES A MININMUM 72" |
| | WIDE CORRIDOR FOR GROUP E OCCUPANCIES. |
| | CORRIDOR #138 DOES NOT COMPLY. |
| | |
| | THE PLANS AND SPECIFICATIONS DO NOT |
| | DECLARE THE METHOD OF HURRICANE MISSILE |
| | IMPACT RESISTANCE IN ACCORDANCE WITH |
| | FBC 1606.1.4. |
| | |
| | IF TEST AND OR NOTICE OF ACCEPTANCE |
| | REPORTS FOR THE EXTERIOR DOORS, WINDOWS |
| | AND ROOF COVERINGS ARENOT INCLUDED |
| | WITH THIS PERMIT APPLICATION, A |
| | SEPARATE PERMIT AND ADDITIONAL FEES |
| | WILL BE REQUIRED. |
| | |
| | BEFORE A PERMIT TO CONSTRUCT MAY BE |
| | ISSUED IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, THE PERMIT PLANS STAMPED |
| | BY THAT OFFICE AND A COPY OF THE PAID |
| | RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION.CALL 561-233-5025 FOR |
| | MORE INFORMATION. |