| Plan Review Notes For Permit 02111446 |
| Permit Number |
02111446 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-11-22 00:00:00 | 1) BUILDING ADDRESS REQUIRED. | | | | | | 2) SINCE NO FIRE SPRINKLERS ARE PLANNED, | | | ALL SERVICE AND STORAGE ROOMS ARE TO | | | BE AT LEAST ONE HOUR FIRE RATED WITH | | | PROPER OPENING PROTECTIVES. | | | | | | 3) PANIC HARDWARE REQUIRED ON ALL EXIT | | | DOORS SINCE OCCUPANT LOADS OF 100 OR | | | MORE PERSONS ARE EXPECTED. | | | | | | 4) A KNOX-BOX WILL BE REQUIRED FOR | | | ENTRY INTO THE CLUBHOUSE. | | | | | | 5) THE FRENCH DOORS THAT ARE NEAR THE | | | DIRECTIONAL EXIT SIGN DOES NOT PROVIDE | | | FOR THE MINIMUM DOOR WIDTH REQUIRED. | | | THE USE OF A SINGLE DOOR FOR EXITING | | | DOES NOT APPEAR TO BE WIDE ENOUGH. | | | PLEASE SEE NFPA 101, THE LIFE SAFETY | | | CODE, SECTION 7.2.1.2.3. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|