2002-11-22 00:00:001) BUILDING ADDRESS REQUIRED.
  
 2) SINCE NO FIRE SPRINKLERS ARE PLANNED,
 ALL SERVICE AND STORAGE ROOMS ARE TO
 BE AT LEAST ONE HOUR FIRE RATED WITH
 PROPER OPENING PROTECTIVES.
  
 3) PANIC HARDWARE REQUIRED ON ALL EXIT
 DOORS SINCE OCCUPANT LOADS OF 100 OR
 MORE PERSONS ARE EXPECTED.
  
 4) A KNOX-BOX WILL BE REQUIRED FOR
 ENTRY INTO THE CLUBHOUSE.
  
 5) THE FRENCH DOORS THAT ARE NEAR THE
 DIRECTIONAL EXIT SIGN DOES NOT PROVIDE
 FOR THE MINIMUM DOOR WIDTH REQUIRED.
 THE USE OF A SINGLE DOOR FOR EXITING
 DOES NOT APPEAR TO BE WIDE ENOUGH.
 PLEASE SEE NFPA 101, THE LIFE SAFETY
 CODE, SECTION 7.2.1.2.3.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910