| Notes |
| Date |
Text |
| 2002-11-25 00:00:00 | **************** UNSAT ************ | | | | | | 1)NOTE: PLEASE NOTE, DISC`S REQ`D FOR | | | A/C AHU`S. 440-11. SHOWN ONLY AS J-BOX. | | | | | | 2)NOTE: PLEASE CLARIFY RECEPT REQ`D FOR | | | SERVICING EQUIPMENT. 210-63 | | | | | | 3)NOTE:PLEASE SEE NOTE AT BOTTOM OF | | | PANEL DP. NOTE #1: MENTIONS GFI BRKR | | | AND THERE IS ALREADY A NOTE #1? | | | PLEASE CORRELATE. | | | | | | 4)NOTE: PLEASE SHOW LOAD CALCULATIONS, | | | 220-3,220-10,220-11,220-13 ETC, PLEASE | | | ALSO NOTE ALL CONTINUOUS LOADS ARE TO BE | | | SHOWN AT 125%. 215-3,230-42. | | | PLEASE SHOW TRACK LIGHTING LOADS PER | | | 220-12B. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|