Plan Review Notes
Plan Review Notes For Permit 02111442
Permit Number 02111442
Review Stop B
Sequence Number 3
Notes
Date Text
2004-01-29 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SUBMIT TWO COPIES OF LEGIBLE,
 COMPLETE PRODUCT APPROVALS.SEPARATE
 PERMITS WILL BE REQUIRED FOR ANY ITEMS
 NOT PROPERLY SUBMITTED BEFORE ISSUANCE.
 PRODUCT APPROVALS MAY BE AVAILABLE AT
 WWW.MIAMIDADE.GOV (FIND A DEPARTMENT,
 BUILDING CODE COMPLIANCE, PRODUCT
 CONTROL SEARCH).
  
 2.)PROVIDE A HURRICANE SHUTTER
 INSTALLATION SCHEDULE AS PER MISSILE
 IMPACT POLICY, SEE ATTACHED.
  
 3.)THE APPROVED ZONING SITE PLAN
 IS NOT IN THE PACKAGE.PLEASE PROVIDE.
  
 4.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 5.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 6.)SINGLE HUNG 24 AND 34 WINDOWS DO
 NOT COMPLY WITH FBC1005.4.
  
 7.)THE WINDOWS AT THE BATH TUBS ARE
 TO COMPLY WITH FBC2405.1 (SAFETY GLASS).
  
 8.)AS PER A CONVERSATION WITH THE
 HOMEOWNER, THE PLAN SHOWS TWO WINDOWS
 IN THE EXISTING BEDROOM ADJACENT TO THE
 ADDITION, BUT THERE IS ONLY ONE.PROVIDE
 A NEW WINDOW TO COMPLY WITH FBC1005.4
 TO PROVIDE EMERGENCY EGRESS FOR THE
 EXISTING BEDROOM.
  
 9.)TWO COPIES OF ENERGY CALCS
 REQUIRED, SIGN OWNER/AGENT LINE
 FBC13-101.2.
  
 10.) THE TITLE BLOCK FOR THE ENGINEER
 IS TO BE ON EVERY PAGE, INCLUDE THE
 LICENSE NUMBER FAC61G15-23.002.