| 2004-01-29 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)SUBMIT TWO COPIES OF LEGIBLE, |
| | COMPLETE PRODUCT APPROVALS.SEPARATE |
| | PERMITS WILL BE REQUIRED FOR ANY ITEMS |
| | NOT PROPERLY SUBMITTED BEFORE ISSUANCE. |
| | PRODUCT APPROVALS MAY BE AVAILABLE AT |
| | WWW.MIAMIDADE.GOV (FIND A DEPARTMENT, |
| | BUILDING CODE COMPLIANCE, PRODUCT |
| | CONTROL SEARCH). |
| | |
| | 2.)PROVIDE A HURRICANE SHUTTER |
| | INSTALLATION SCHEDULE AS PER MISSILE |
| | IMPACT POLICY, SEE ATTACHED. |
| | |
| | 3.)THE APPROVED ZONING SITE PLAN |
| | IS NOT IN THE PACKAGE.PLEASE PROVIDE. |
| | |
| | 4.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY. THE PLANS MUST BE |
| | STAMPED AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION.233-5025 |
| | |
| | 5.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 6.)SINGLE HUNG 24 AND 34 WINDOWS DO |
| | NOT COMPLY WITH FBC1005.4. |
| | |
| | 7.)THE WINDOWS AT THE BATH TUBS ARE |
| | TO COMPLY WITH FBC2405.1 (SAFETY GLASS). |
| | |
| | 8.)AS PER A CONVERSATION WITH THE |
| | HOMEOWNER, THE PLAN SHOWS TWO WINDOWS |
| | IN THE EXISTING BEDROOM ADJACENT TO THE |
| | ADDITION, BUT THERE IS ONLY ONE.PROVIDE |
| | A NEW WINDOW TO COMPLY WITH FBC1005.4 |
| | TO PROVIDE EMERGENCY EGRESS FOR THE |
| | EXISTING BEDROOM. |
| | |
| | 9.)TWO COPIES OF ENERGY CALCS |
| | REQUIRED, SIGN OWNER/AGENT LINE |
| | FBC13-101.2. |
| | |
| | 10.) THE TITLE BLOCK FOR THE ENGINEER |
| | IS TO BE ON EVERY PAGE, INCLUDE THE |
| | LICENSE NUMBER FAC61G15-23.002. |