| 2004-05-05 00:00:00 | *********** UNSAT ************** |
| | |
| | 1)NOTE: PLEASE SEE FAC/ FS, PLANS SIGNED |
| | AND SEALED BY AN ARCH/ ENG MUST CONTAIN |
| | A TITLE BCLOCK W/ ALL INFORMATION AS |
| | SET FORTH IN FAC 61G1-16.004, 61G15-23. |
| | 002. |
| | |
| | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | SERVICE NEW? |
| | |
| | 3)) NOTE: PLEASE SEE MISSING RECEPTS FOR |
| | FRONT AND/OR REAR OF DWELLING. |
| | 210.52E |
| | |
| | 4) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | MASTER BEDROOM. |
| | |
| | 5 )NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | 2002 NEC 210.12 |
| | |
| | 6)NOTE: PLEASE SEE MAX OCP FOR WATER |
| | HEATER IS 150%, MIN 125%/ SHOWN AS 2P30A |
| | FOR 3.5 KW. |
| | |
| | 7)NOTE; PLEASE SEE FBC, ADDITIONS TO |
| | EXISTING DWELLINGS OF 25% OR MORE. |
| | PLEASE SHOW ALL EXISITING ELECTRICAL |
| | THAT MEETS CODE AND/OR NEW ELECTRICAL |
| | THAT IS REQ'D TO BROUGHT UP TO CODE |
| | IN EXSITING BLDG. RECEPT/LTS/SD'S ETC. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |