2002-11-20 00:00:00PROVISO:
  
 AS PER NFPA 33
 3.3.2, A CLEAR SPACE OF NOT LESS THAN 3
 FT SHALL BE MAINTAINED ONALL SIDES OF
 THE SPRAY BOOTH.
  
 5.4, THE EXHAUST DUCT DISCHARGE POINT
 SHALL BE AT LEAST 6 FT FROM ANY EXTERIOR
 WALL OR ROOF.
  