| Notes |
| Date |
Text |
| 2002-11-20 00:00:00 | PROVISO: | | | | | | AS PER NFPA 33 | | | 3.3.2, A CLEAR SPACE OF NOT LESS THAN 3 | | | FT SHALL BE MAINTAINED ONALL SIDES OF | | | THE SPRAY BOOTH. | | | | | | 5.4, THE EXHAUST DUCT DISCHARGE POINT | | | SHALL BE AT LEAST 6 FT FROM ANY EXTERIOR | | | WALL OR ROOF. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|