| Plan Review Notes For Permit 02111287 |
| Permit Number |
02111287 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-11-21 00:00:00 | 1) SPRAY BOOTH IS TO BE PROPERLY | | | GROUNDED. | | | | | | 2) SPRAY BOOTH SHALL PROVIDE FOR | | | AT LEAST THREE FEET OF CLEARANCE | | | AROUND IT TO PROVIDE FOR CLEANING. | | | | | | 3) SPRAY BOOTH TO BE PROTECTED BY | | | AN APPROVED EXTINGUISHING SYSTEM. | | | SEPARATE PLANS AND PERMITS REQUIRED. | | | | | | 4) FILTERS TO MEET UL REQUIREMENTS. | | | | | | 5) APPROVED UL FLAMMABLE OR | | | COMBUSTIBLE CABINETS ARE TO BE | | | PROVIDED FOR THE STORAGE OF FLAMMABLE | | | OR COMBUSTIBLE MATERIALS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|