Plan Review Notes
Plan Review Notes For Permit 02111251
Permit Number 02111251
Review Stop P
Sequence Number 5
Notes
Date Text
2003-07-26 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1) SLEEVE IN CONCRETE NOT APPROVED.
 APPROVED METHOD FOR INSTALLING PIPE IN
 CONCRETE FLOOR SHALL COMPLY WITH SECTION
 404.6.1(2). CONCRETE SHALL BE CUT OUT,
 PIPE INSTALLED, PAINTED WITH A BITUMIN-
 OUS PAINT AND COVERED WITH A LIGHTWEIGHT
 CONCRETE SO THAT THE PIPE CAN BE REMOVED
 IF REQUIRED.
 2) SEE PROVISO FOR APPLICATION FOR GAS
 PERMIT ON SHEET P-101 OF THE APPROVED
 PLANS. AT THIS TIME NO GAS PERMIT HAS
 BEEN APPLIED FOR.
 3) THE HOOD SHUT DOWN SHALL BE BELOW THE
 CEILING, BUT DOES NOT HAVE TO BE AT
 CEILING HEIGHT. (INFORMATIONAL)
  