| Plan Review Notes For Permit 02111251 |
| Permit Number |
02111251 |
|
| Review Stop |
P |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2003-07-26 00:00:00 | DENIED | | | REFERENCE: FBC-2001 FUEL GAS | | | | | | 1) SLEEVE IN CONCRETE NOT APPROVED. | | | APPROVED METHOD FOR INSTALLING PIPE IN | | | CONCRETE FLOOR SHALL COMPLY WITH SECTION | | | 404.6.1(2). CONCRETE SHALL BE CUT OUT, | | | PIPE INSTALLED, PAINTED WITH A BITUMIN- | | | OUS PAINT AND COVERED WITH A LIGHTWEIGHT | | | CONCRETE SO THAT THE PIPE CAN BE REMOVED | | | IF REQUIRED. | | | 2) SEE PROVISO FOR APPLICATION FOR GAS | | | PERMIT ON SHEET P-101 OF THE APPROVED | | | PLANS. AT THIS TIME NO GAS PERMIT HAS | | | BEEN APPLIED FOR. | | | 3) THE HOOD SHUT DOWN SHALL BE BELOW THE | | | CEILING, BUT DOES NOT HAVE TO BE AT | | | CEILING HEIGHT. (INFORMATIONAL) | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|