Plan Review Notes
Plan Review Notes For Permit 02111251
Permit Number 02111251
Review Stop P
Sequence Number 4
Notes
Date Text
2003-07-01 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. THESE
 VALVES AND UNION ARE NOT SHOWN ON RISER.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692