Plan Review Notes
Plan Review Notes For Permit 02111251
Permit Number 02111251
Review Stop P
Sequence Number 3
Notes
Date Text
2003-04-01 00:00:00PASSED/PROVISO
  
 PER DEPT. OF BUSINESS AND PROFESSIONAL
 REGULATION REVIEW, A DIPPERWELL IS REQ-
 UIRED. A REVISION IS REQUIRED FOR THE
 FLOOR PLAN, SANT. RISER AND WATER RISER
 SHOWING DIPPERWELL.
  
 SEPARATE GAS PERMIT REQUIRED. GAS REQ-
 UIREMENTS TO BE SUBMITTED AT TIME OF
 APPLICATION.
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 2. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 4. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.