| 2003-04-01 00:00:00 | PASSED/PROVISO | | | | | | PER DEPT. OF BUSINESS AND PROFESSIONAL | | | REGULATION REVIEW, A DIPPERWELL IS REQ- | | | UIRED. A REVISION IS REQUIRED FOR THE | | | FLOOR PLAN, SANT. RISER AND WATER RISER | | | SHOWING DIPPERWELL. | | | | | | SEPARATE GAS PERMIT REQUIRED. GAS REQ- | | | UIREMENTS TO BE SUBMITTED AT TIME OF | | | APPLICATION. | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2001 | | | FUEL GAS CODE. | | | 2. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2001 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES (A)(3). | | | 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2001 FUEL GAS CODE SEC 402.2 | | | 4. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. |
|