Plan Review Notes
Plan Review Notes For Permit 02111251
Permit Number 02111251
Review Stop E
Sequence Number 3
Notes
Date Text
2003-06-19 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE SEE 700-12E. PLEASE
 CIRCUIT EXT AND EM LT AND CORRELATE
 W/ A SUBMIT REVISED PANEL SCHEDULE.
 PLEASE NOTE, THIS WAS NOTED AND REDLINED
 ON PREVIOUS TWO REVIEWS.
  
 2)NOTE: PLEASE ALSO SUBMIT REVISED
 RISER DIAGRAM W/ EQUIPMENT GROUNDING
 CONDUCTOR BETWEEN MAIN AND PANEL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEYPALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected].