Date Text
2003-02-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 11
  
 1) FROM PREVIOUS REVIEW: PLANS SHALL BE
 ROUTED TO DEPT. OF BUSINESS REGULATION
 HOTEL & RESTURANT DIVISION PRIOR TO RE-
 SUBMITTING TO CITY FOR REVIEW. PLANS
 SHALL BE STAMPED AND WORK SHEETS ATTACH-
 ED TO PLANS.
 2) FROM PREVIOUS REVIEW: SHT P101 WATER
 RISER DIAGRAM, WATER HAMMER ARRESTORS
 SHALL BE LOCATED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE" NOT AT THE TOP OF THE
 DROP IN THE CEILING. PER PDI-WH 201 AND
 MANUF. INSTALLATION INSTRUCTIONS.
 3) DELIVERY PERSSURE OF 2LBS WILL ALLOW
 11,415,000 BTU'S. ON 1-1/4" PIPE. MAY
 I SUGGEST A 1/2 LB. SYSTEM THAT WILL
 ALLOW 950,OOO BTU'S FOR 1-1/4" PIPE, AND
 YOU WILL NOT NEED REGULATORS FROM 2LBS.
 4) FROM PREVIOUS REVIEW:********
 A. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 B. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 REVIEW BY KEN STEVENS