Plan Review Notes
Plan Review Notes For Permit 02111251
Permit Number 02111251
Review Stop M
Sequence Number 2
Notes
Date Text
2003-02-12 00:00:00PROVISO:
 PROVIDE SUBMITTAL FOR THE CONDENSER
 UNIT ROOF STANDS.SHOW COMPLIANCE
 WITH 2001 FBC 1511.7 FOR CLEARANCE
 REQUIREMENTS ABOVE FINISHED ROOF.
  
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRE SUPRESSION & WALK-IN COOLERS.
 PROVIDE PLANS AND MANUFACTURER SUBMITTAL
 DATA WITH PERMIT APPLICATIONS.PROVIDE
 AIR BALANCE SCHEDULE FOR HOOD
 EXHAUST/MAKEUP.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.