| Date |
Text |
| 2002-12-14 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1) PLANS SHALL BE ROUTED TO DEPT. OF |
| | BUSINESS REGULATION HOTEL & RESTURANT |
| | DIVISION (954) 956-5692 PRIOR TO RE- |
| | SUBMITTING TO CITY OF WPB FOR REVIEW. |
| | 2) GREASE TRAP SHALL BE SIZED BY UTILITY |
| | DEPT., WASTE ORD. #2938-96. PLEASE CON- |
| | TACT RODNEY COMPO ENVIRONMENTAL COMPLI- |
| | ANCE (561) 837-4074. |
| | 3) RPZ BACKFLOW IS REQUIRED FOR WATER |
| | SERVICE TO RESTURANT. MAX 4' ABOVE FLOOR |
| | FOR SERVICE AND CERTIFICATION. |
| | 4) SHT A100 TOILET ROOMS SHALL COMPLY |
| | WITH SECTION 11-4.22. SHOW CLEAR FLOOR |
| | SPACE, AND UNOBSTRUCTED 5' TURNING RAD- |
| | IUS. 11-4.22.3. DOOR SHALL NOT OPEN INTO |
| | THE CLEAR FLOOR SPACE OR TURNING RADIUS |
| | OF ANY FIXTURE. SECTION 11-4.22.2. |
| | SEC 11-4.16 AND ALL SUBSECTIONS - |
| | SEC 11-4.19 AND ALL SUBSECTIONS - PLEASE |
| | PROVIDE DETAILS FOR COMPLIANCE. |
| | 5) SHTS P100 & P101, FLOOR SINKS ARE RE- |
| | QUIRED FOR ALL INDIRECT WASTE. 802.3 |
| | FLOOR DRAINS ARE NOT AN APPROVED INDIR- |
| | ECT WASTE RECEPTOR. |
| | 6) SHTS P100 & P101 DISHWASHER SHALL |
| | DRAIN INTO THE SANITARY SYSTEM NOT THE |
| | GREASE LINE PER UTILITY DEPT. |
| | 7) SHTS P100P101 WATER RISER DIAGRAM. |
| | WATER HAMMER ARRESTORS ARE REQUIRED AT |
| | ALL QUICK CLOSING VALVES, (ICE MACHINE, |
| | DISHWASHER) PER 406.9. THE LOCATION |
| | SHALL BE IN AN "EFFECTIVE RANGE" NEAR |
| | THE FIXTURE, NOT AT THE TOP OF THE DROP |
| | IN CEILING PER PDI-WH 201 AND MANUFACT- |
| | URE INSTALLATION INSTRUCTIONS. |
| | 8) SHTS P100 & P101 VENT REQUIRED FOR |
| | GREASE LINE AS IT ENTERS BLDG TO VENT |
| | GREASE TANK. |
| | 9) THE FOLLOWING COMMENTS ARE FOR THE |
| | NATURAL GAS SYSTEM. INFORMATION REQUIRED |
| | FOR GAS PERMIT APPLICATION. (SEPARATE |
| | PERMIT REQUIRED) |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | GAS CODE. |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | 4. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | FBC-2001 FUEL GAS CODE SEC. 401.8 THRU |
| | 402.5.2 & TABLES 402(1) THRU 402(34). |
| | 5. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). |
| | 7. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC 402.2. IF |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND FBC-2001 |
| | FUEL GAS CODE SEC. 402.2 |
| | 12. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |