Text |
| 2002-12-05 00:00:00 | 1) PLANS DO NOT INDICATE ANY INTERIOR | | | FINISH CLASSIFICATION FOR THE WALLS | | | AND CEILINGS. | | | | | | 2) TABLES AND CHAIRS APPEAR TO BE TOO | | | CLOSE TOGETHER IN SOME LOCATIONS. | | | | | | 3) AN EXIT SIGN IS PRESENT DIRECTING | | | PERSONS TO EXIT THU KITCHEN. THIS IS | | | NOT ALLOWED. PLEASE REVISE PLANS AS | | | NECESSARY. | | | | | | 4) NO FIRE ALARM EQUIPMENT SHOWN IN | | | TENANT SPACE. PLEASE DISPLAY FIRE | | | ALARM EQUIPMENT ON THE PLANS. | | | | | | 5) PLEASE EXPLAIN HOW THE TWO EXITS | | | LOCATED AWAY FROM THE KITCHEN ARE | | | PROPERLY SEPARATED FROM ONE ANOTHER. | | | | | | 6) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR ANY HOOD, DUCT, AND FIRE SUPPRESSION | | | SYSTEMS PLANNED FOR THE LOCATION. | | | | | | 7) SEPARATE PLANS AND PERMITS FOR FIRE | | | ALARM EQUIPMENT. | | | | | | 8) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR FIRE SPRINKLER MODIFICATIONS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|