| Plan Review Notes For Permit 02111251 |
| Permit Number |
02111251 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-11-25 00:00:00 | ************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE, PLANS MUST CONTAIN | | | ORIG SIGNATURE FROM THE ENGINEER/ARCH | | | OF RECORD. AN INK STAMP IS NOT ACCEPTED | | | BY FS 471.025/481.221. | | | | | | 2)NOTE: PLEASE NOTE, LOAD CALCULATIONS | | | NEED TO BE SHOWN, PLEASE NOTE ALL | | | CONTINUOUS LOADS ARE TO BE SHOWN AT | | | 125% 230-42/215-3 | | | | | | 3)NOTE: PLEASE NOTE, ALL CIRCUITING | | | NEEDS TO BE SHOWN, PLEASE NOTE, CIRCUITS | | | FOR EM/EXT LTS PER 700-12E. | | | | | | 4)NOTE: PLEASE NOTE, SHOW WINDOW RECEPTS | | | REQ`D 210-62. | | | | | | 5)NOTE: PLEASE CLARIFY MEANS OF EQUIP- | | | -MENT GROUNDING BETWEEN MAIN DISC AND | | | PANEL "E".EQUIP GRND, SIZE PER 250-122 | | | | | | 6)NOTE: PLEASE SUBMIT AIC RATING FOR | | | NEW MAIN DISCONNECT SHOWN. | | | MAINS/PANELS/BREAKERS ALL MUST BE RATED | | | FOR THE AVAILABLE FAULT CURRENT PER | | | 110-9. | | | | | | 7)NOTE: PLEASE PROVIDE LOAD FOR EXISTING | | | MAIN. PLEASE NOTE, THIS SERVICE IS | | | SHOWN ADDING 197A`S. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|