Plan Review Notes
Plan Review Notes For Permit 02111251
Permit Number 02111251
Review Stop E
Sequence Number 1
Notes
Date Text
2002-11-25 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE, PLANS MUST CONTAIN
 ORIG SIGNATURE FROM THE ENGINEER/ARCH
 OF RECORD. AN INK STAMP IS NOT ACCEPTED
 BY FS 471.025/481.221.
  
 2)NOTE: PLEASE NOTE, LOAD CALCULATIONS
 NEED TO BE SHOWN, PLEASE NOTE ALL
 CONTINUOUS LOADS ARE TO BE SHOWN AT
 125% 230-42/215-3
  
 3)NOTE: PLEASE NOTE, ALL CIRCUITING
 NEEDS TO BE SHOWN, PLEASE NOTE, CIRCUITS
 FOR EM/EXT LTS PER 700-12E.
  
 4)NOTE: PLEASE NOTE, SHOW WINDOW RECEPTS
 REQ`D 210-62.
  
 5)NOTE: PLEASE CLARIFY MEANS OF EQUIP-
 -MENT GROUNDING BETWEEN MAIN DISC AND
 PANEL "E".EQUIP GRND, SIZE PER 250-122
  
 6)NOTE: PLEASE SUBMIT AIC RATING FOR
 NEW MAIN DISCONNECT SHOWN.
 MAINS/PANELS/BREAKERS ALL MUST BE RATED
 FOR THE AVAILABLE FAULT CURRENT PER
 110-9.
  
 7)NOTE: PLEASE PROVIDE LOAD FOR EXISTING
 MAIN. PLEASE NOTE, THIS SERVICE IS
 SHOWN ADDING 197A`S.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372