2002-12-18 00:00:001) IF FS 553.895 (2) IS BEING REFERENCED
 THEN THE PLANS SHOULD ALSO MAKE
 REFERENCE THAT A 20 FOOT SEPARATION
 IS REQUIRED BETWEEN THE BUILDING AND
 PARKING GARAGE THUS ALLOWING THE
 EXCEPTION TO THE STATUE FOR OPEN PARKING
 GARAGES NOT BEING SPRINKLER PROTECTED.
  
 2) ALL SHAFTS THAT ARE LARGE ENOUGH FOR
 PERSONS TO FALL INTO MUST BE IDENTIFIED
 WITH SIGNAGE INDICATING "SHAFTWAY" IN
 SIX INCH HIGH RED LETTERS ON A WHITE
 BACKGROUND.
  
 3) PLEASE INDICATE PRESCRIPTIVE
 STRENGTH REQUIREMENTS FOR 43"CHAIN LINK
 FENCE INSIDE WALL AT OPENINGS.
  
 4) TITLE PAGE AND ELECTRICAL PAGES DO
 NOT MATCH. TITLE PAGE INDICATES NO
 FIRE ALARM SYSTEM BUT ELECTRICAL PAGES
 DISPLAYS A FIRE ALARM SYSTEM.
  
 5) PLANS DO NOT REFLECT STANDPIPE
 SYSTEM INSTALLATION. ONLY CALCULATIONS
 FOR THE STANDPIPE HAS BEEN PROVIDED.
 ONLY ONE SET OF PLANS WERE LOCATED.