| Plan Review Notes For Permit 02111234 |
| Permit Number |
02111234 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-12-18 00:00:00 | 1) IF FS 553.895 (2) IS BEING REFERENCED | | | THEN THE PLANS SHOULD ALSO MAKE | | | REFERENCE THAT A 20 FOOT SEPARATION | | | IS REQUIRED BETWEEN THE BUILDING AND | | | PARKING GARAGE THUS ALLOWING THE | | | EXCEPTION TO THE STATUE FOR OPEN PARKING | | | GARAGES NOT BEING SPRINKLER PROTECTED. | | | | | | 2) ALL SHAFTS THAT ARE LARGE ENOUGH FOR | | | PERSONS TO FALL INTO MUST BE IDENTIFIED | | | WITH SIGNAGE INDICATING "SHAFTWAY" IN | | | SIX INCH HIGH RED LETTERS ON A WHITE | | | BACKGROUND. | | | | | | 3) PLEASE INDICATE PRESCRIPTIVE | | | STRENGTH REQUIREMENTS FOR 43"CHAIN LINK | | | FENCE INSIDE WALL AT OPENINGS. | | | | | | 4) TITLE PAGE AND ELECTRICAL PAGES DO | | | NOT MATCH. TITLE PAGE INDICATES NO | | | FIRE ALARM SYSTEM BUT ELECTRICAL PAGES | | | DISPLAYS A FIRE ALARM SYSTEM. | | | | | | 5) PLANS DO NOT REFLECT STANDPIPE | | | SYSTEM INSTALLATION. ONLY CALCULATIONS | | | FOR THE STANDPIPE HAS BEEN PROVIDED. | | | ONLY ONE SET OF PLANS WERE LOCATED. | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|