Plan Review Notes
Plan Review Notes For Permit 02111234
Permit Number 02111234
Review Stop E
Sequence Number 1
Notes
Date Text
2002-12-09 00:00:00*********** UNSAT ***********
  
 1)NOTE: PLEASE CLARIFY LIGHTING IN
 ELEV / ELC RM TO MEET 700-16
  
 2)NOTE: PLEASE SHOW GROUNDING ELECTRODE
 TO FOOTER STEEL AN COLD WATER(IF ANY)
 PER 250-50.
  
 3)NOTE: PLEASE CLARIFY OCP FOR FIRE
 PUMP, PLEASE SEE 695-4. RATED FOR LOCK
 ROTOR.
  
 4)NOTE: PLEASE CLARIFY METHOD OF EQUIP-
 -MENT GROUNDING BETWEEN MAIN DISC AND
 PANEL/FIRE PUMP. 250-24/250-122
  
 5)NOTE: PLEASE CLARIFY GROUND FOR
 TRANSFORMER PER 250-30
  
 6)NOTE: PLEASE CLARIFY METHOD OF EQUIP-
 -MENT ON MAIN SERVICE ALSO/ BETWEEN MAIN
 /DISC`S , PANEL A AND PANEL B. ETC.
 SIZE PER 250-122.
  
 7)NOTE: PLEASE NOTE, ALL CONTINUOUS
 LOADS NEED TO BE SHOWN AT 125%.(LIGHTING
 ). 215-3/230-42 ETC.
  
 8)NOTE; PLEASE NOTE, AS PER LOCAL AMEND-
 -MENTS, NO ALUM CONDUCTORS MAY BE USED
 FOR GROUNDING OR BONDING. PLEASE ALSO
 NOTE, NO ALUM CONDUCTORS ARE PERMITTED
 FOR ANY PURPOSE SMALLER THAN #2.
 250-62/310-2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  