| Plan Review Notes For Permit 02111234 |
| Permit Number |
02111234 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-12-09 00:00:00 | *********** UNSAT *********** | | | | | | 1)NOTE: PLEASE CLARIFY LIGHTING IN | | | ELEV / ELC RM TO MEET 700-16 | | | | | | 2)NOTE: PLEASE SHOW GROUNDING ELECTRODE | | | TO FOOTER STEEL AN COLD WATER(IF ANY) | | | PER 250-50. | | | | | | 3)NOTE: PLEASE CLARIFY OCP FOR FIRE | | | PUMP, PLEASE SEE 695-4. RATED FOR LOCK | | | ROTOR. | | | | | | 4)NOTE: PLEASE CLARIFY METHOD OF EQUIP- | | | -MENT GROUNDING BETWEEN MAIN DISC AND | | | PANEL/FIRE PUMP. 250-24/250-122 | | | | | | 5)NOTE: PLEASE CLARIFY GROUND FOR | | | TRANSFORMER PER 250-30 | | | | | | 6)NOTE: PLEASE CLARIFY METHOD OF EQUIP- | | | -MENT ON MAIN SERVICE ALSO/ BETWEEN MAIN | | | /DISC`S , PANEL A AND PANEL B. ETC. | | | SIZE PER 250-122. | | | | | | 7)NOTE: PLEASE NOTE, ALL CONTINUOUS | | | LOADS NEED TO BE SHOWN AT 125%.(LIGHTING | | | ). 215-3/230-42 ETC. | | | | | | 8)NOTE; PLEASE NOTE, AS PER LOCAL AMEND- | | | -MENTS, NO ALUM CONDUCTORS MAY BE USED | | | FOR GROUNDING OR BONDING. PLEASE ALSO | | | NOTE, NO ALUM CONDUCTORS ARE PERMITTED | | | FOR ANY PURPOSE SMALLER THAN #2. | | | 250-62/310-2 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|