| Date |
Text |
| 2003-01-08 00:00:00 | |
| | BUILDING PLAN REVIEW |
| | PERMIT:02111234 |
| | ADD: 616 CLEARWATER PARK RD |
| | CONT: FINFROCK CONSTRUCTION |
| | TEL: (407)293-4000 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2) 105.3 INSPECTION SERVICE, RESIDENT |
| | INSPECTOR REQUIRED FOR BUILDINGS 3 STOR- |
| | IES AND MORE. |
| | |
| | 3) TABLE 600 ISSUES NORTH FACE OVER THE |
| | ALLOWABLE 20%. EXAMPLE 10.5'X 122.66= |
| | 1287.93 FTX20%= ALLOWABLE OPENINGS OF |
| | 257.58 SQ FT. SECOND FLOOR |
| | THIRD FLOOR OVER BY 10 SQ FT , 1ST FLOOR |
| | OK! IN DECREASING THE ALLOWABLE AREA ON |
| | THE SECOND FLOOR THE % OF OPENINGS IS |
| | 21.34 % |
| | |
| | 4) 11-4.6.5 PLEASE PROVIDE THE VERTICAL |
| | CLEARENCE FOR ACCESSIBLE VAN AND THE |
| | PASSENGER LOADING ZONE. |
| | |
| | 5)FL. BLD CODE 1606.1.7 THE FOLLOWING |
| | INFORMATION RELATED TO WIND SHALL BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | MISSING INFORMATION? |
| | |
| | 6) 1707.4.3 EACH EXTERIOR DOOR |
| | ASSEMBLY NOT COVERED BY 1707.4.2 |
| | (GLAZED DOORS) SHALL BE LISTED AND TEST- |
| | ED FOR A PERIOD EQUAL TO THE QUANITY |
| | 3600/ V WHERE THE TIME PERIOD IS IN |
| | SECTIONS AND V IS IN MILES PER HR TAKEN |
| | FROM FIGURE 1606. THE TIME PERIOD SHALL |
| | ALSO INCLUDE A 10 SECOND PERIOD AT A |
| | LOAD EQUAL TO 1.5 TIMES THE DESIGN |
| | PRESSURE. DADE COUNTY & SBCCI REPORTS |
| | ARE ACCEPTED. |
| | |
| | 7)3003.6.1 VENTS. HOISTWAYS OF ELEVA- |
| | TORS SERVING MORE THAN 3 FLOORS SHALL BE |
| | PROVIDED WITH MEANS OF VENTING SMOKE |
| | AND HOT GASES TO THE OUTER AIR IN CASE |
| | OF FIRE. |
| | |
| | 8)3003.6.2 VENTS SHALL BE LOCATED |
| | BELOW THE FLOOR OR FLOORS AT THE TOP OF |
| | THE HOISTWAY, AND SHALL BE EITHER DIR- |
| | ECTLY TO THE OUTER AIR OR THROUGH NON- |
| | COMBUSTIBLE DUCTS TO THE OUTER AIR. |
| | |
| | 9)3003.6.3 THE AREA OF THE VENTS |
| | SHALL BE NOT LESS THAN 3 SQ FT FOR EACH |
| | ELEVATOR CAR, WHICHEVER IS GREATER. |
| | |
| | 10)FL BLD CODE 1804.2.2 QUESTIONABLE |
| | SOILS, WHERE THE BEARING CAPACITY IS |
| | NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| | |
| | 11)BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| | DESCRIPTION OF THE REVISION MADE, IDEN- |
| | TIFYING THE SHEET OR SPECIFICATION PAGE |
| | WHERE THE CHANGES CAN BE FOUND, WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | JIM WITMER |
| | PLAN REVIEW |
| | TEL: (561)659-8096 EX.8412 |
| | FAX: (561)659-8026 |