| Plan Review Notes For Permit 02111090 |
| Permit Number |
02111090 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-12-10 00:00:00 | DENIED: | | | | | | 1.PLAN SHEET M-1 INDICATES PVC | | | CONDENSATE IN THE RETURN AIR PLENUM. | | | AS PER 2001 FBC(M) 602.2.1 MATERIALS | | | EXPOSED WITHIN PLENUMS SHALL BE | | | NONCOMBUSTIBLE. | | | | | | 2.CLARIFY NEW 36" X 24" CURTIN TYPE | | | FIRE DAMPER FOR FRESH AIR FROM | | | EXISTING BUILDING ON PLAN SHEET M-1, | | | DEMONSTRATE HOW "RECIRCULATED AIR" | | | FROM ANOTHER OCCUPANCY IS CONSIDERED | | | FRESH AIR.REFERENCE 2001 FBC(M) | | | 403.2.1 #1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|