2002-12-10 00:00:00DENIED:
  
 1.PLAN SHEET M-1 INDICATES PVC
 CONDENSATE IN THE RETURN AIR PLENUM.
 AS PER 2001 FBC(M) 602.2.1 MATERIALS
 EXPOSED WITHIN PLENUMS SHALL BE
 NONCOMBUSTIBLE.
  
 2.CLARIFY NEW 36" X 24" CURTIN TYPE
 FIRE DAMPER FOR FRESH AIR FROM
 EXISTING BUILDING ON PLAN SHEET M-1,
 DEMONSTRATE HOW "RECIRCULATED AIR"
 FROM ANOTHER OCCUPANCY IS CONSIDERED
 FRESH AIR.REFERENCE 2001 FBC(M)
 403.2.1 #1.
  