Plan Review Notes
Plan Review Notes For Permit 02111090
Permit Number 02111090
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-11-22 00:00:001) PLANS MAKE REFERENCE TO SECURITY
 DEVICES INSTALLED ON EXIT DOORS. PLEASE
 BE ADVISED THAT SECURITY DEVICES ARE
 TO MEET ACCESS CONTROLLED OR DELAYED
 EGRESS REQUIREMENTS. PLEASE REVISE
 PLANS AS NECESSARY.
  
 2) SINGLE AND DOUBLE DOORS APPEAR TO
 OPPOSE ONE ANOTHER IN CORRIDOR.
  
 3) ALL DOORS INSTALLED WITHIN THE
 CORRIDOR SYSTEM ARE TO BE FIRE RATED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910