| Plan Review Notes For Permit 02111043 |
| Permit Number |
02111043 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-12-06 00:00:00 | ************ UNSAT ***************** | | | | | | 1)NOTE: PLEASE NOTE, ALL CONTINUOUS | | | LOADS ARE TO BE SHOWN AT 125%. | | | 215-3/230-42 | | | | | | 2)NOTE: PLEASE SHOW/CLARIFY LOAD ON | | | EXISTING 1200A MAIN W/ NEW PANEL LOAD | | | BEING ADDED. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|