2002-12-06 00:00:00************ UNSAT *****************
  
 1)NOTE: PLEASE NOTE, ALL CONTINUOUS
 LOADS ARE TO BE SHOWN AT 125%.
 215-3/230-42
  
 2)NOTE: PLEASE SHOW/CLARIFY LOAD ON
 EXISTING 1200A MAIN W/ NEW PANEL LOAD
 BEING ADDED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372