| Plan Review Notes For Permit 02111030 |
| Permit Number |
02111030 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-12-11 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | 1) SHT A.1 PER 11-4.1.6(1)(A) BOTH | | | TOILET ROOMS SHALL BE ACCESSIBLE. | | | 2) SHT A.1 PER SEC 403.2 SEPARATE FAC- | | | ILITIES ARE REQUIRED FOR EACH SEX. | | | (EXCEPTION #4 3000 SQ FT OR LESS) | | | 3) SHT A.1 PER TABLE 403.1 A DRINKING | | | FOUNTAIN IS REQUIRED. ALSO SEE SECTION | | | 410.1 | | | 4) SHT A.1 SINK IN KITCHEN SHALL COMPLY | | | WITH SECTION 11-4.24 AND ALL SUBSECTIONS | | | PLEASE PROVIDE DETAIL. | | | 5) PLEASE SHOW ALL CLEAR FLOOR SPACES | | | FOR ACCESSIBLE FIXTURES. ALSO SHOW 5' | | | TURNING RADIUS'S. | | | 6) PLEASE SUBMIT A SANITARY AND A WATER | | | RISER DIAGRAM. ON WATER RISER DIAGRAM, | | | SHOW WATER HAMMER ARRESTORS REQUIRED BY | | | SECTION 406.9. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|