| 2002-11-20 00:00:00 | **************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE NOTE PLANS NOTE 3 NEW | | | SCONCES AND ONLY 2 SHOWN. | | | | | | 2)NOTE: PLEASE ALSO SEE 700-12E FOR | | | CIRCUITING OF EM/EX LTS. | | | | | | 3)NOTE: PLEASE CLARIFY LOADS AND SIZE | | | OF EXISTING ELEC, CHANGING USE FROM | | | RESIDENTIAL TO COMM USE. PER 220 | | | | | | 4)NOTE: PLEASE CLARIFY IF NEW HC BATH | | | IS FROM AN EXISTING LOCATION? W/ EXIST | | | ELEC OR NEW ? | | | | | | 5)NOTE: PLEASE CLARIFY NEW "WORK" | | | STATIONS SHOWN ON PLANS. WILL THEY HAVE | | | ELECTRIC? | | | | | | 6)NOTE: PLEASE PROVIDE CIRCUITING ON | | | PLANS AND CORRELATE W/ A PANEL SCHEDULE. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|