Plan Review Notes
Plan Review Notes For Permit 02111030
Permit Number 02111030
Review Stop B
Sequence Number 1
Notes
Date Text
2002-12-12 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) FBC* 104.2.1.2PLANS SHALL STATE THE
 FLOOR AREA, AND THE EXISTING AND
 PROPOSED OCCUPANCY CLASSIFICATION.
  
 3) FBC* 104.2.1.2AMEND THE PLANS TO
 CLEARLY SHOW WHICH ARE EXISTING WALLS
 AND DOORS, AND WHERE NEW OPENINGS ARE TO
 BE FORMED IN EXISTING WALLS.
  
 4) FBC* 104.2.1.2PROVIDE A CROSS-
 SECTION THROUGH THE CONFERENCE 1 WALL TO
 CLARIFY THE PROPOSED ARRANGEMENT FOR THE
 "NEW INSULATED WALL" AND "3 1/2 INCH
 WALL TRAY" IN RELATION TO THE EXISTING
 WALL.WHAT DOES THE HEAVY BLACK LINE ON
 THE PLAN REPRESENT?
  
 5) FBC 11-7.2(2)THE RECEPTION COUNTER
 SHALL HAVE A PORTION NOT LESS THAN 36"
 LONG WITH A MAXIMUM HEIGHT OF 36" ABOVE
 FLOOR LEVEL.ALTERNATIVELY AN AUXILIARY
 COUNTER WITH A MAXIMUM HEIGHT OF 36"
 SHALL BE PROVIDED IN CLOSE PROXIMITY TO
 THE MAIN COUNTER.
  
 6) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499