| Notes |
| Date |
Text |
| 2002-12-11 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-PROVIDE COMPLETE INFORMATION FOR STORM | | | SHUTTERS UNDER A SEPARATE PERMIT. | | | 2-FLOOD ZONE A8. WILL NEED THE ELEVATION | | | CERTIFICATE. | | | 3-2ND FLOOR FRAMING PLAN: SPECIFY | | | DRAFSTOPPING LOCATION AT AREAS NOT TO | | | EXCEED 500 S.F. AS REQUIRED BY SECTION | | | 2305.2.2 FBC 2001. | | | 4-SPECIFY SIZE OF ANCHOR BOLT AND WASHER | | | FOR GARAGE DOOR STRUCTURAL BUCK DETAIL | | | SE. 104.2.1.2 CITY AMENDMENTS TO FBC. | | | 5-24SH AND 34SH WINDOWS DON'T PROVIDE | | | THE 24" MIN. CLEAR HEIGHT OPENING AS | | | REQUIRED BY SEC. 105.4.4 FBC 2001. | | | ALSO, 24SH WINDOWS DON'T PROVIDE THE | | | 5.7 S.F. MIN. CLEAR OPENING. REVISE | | | CLARIFY AS REQUIRED. | | | 6-DETAIL S21 DOESN'T WORK FOR WOOD COL. | | | P1 LOCATED BET. GARAGE & STAIRWAY. | | | REVISE/ CLARIFY AS REQUIRED. SEC. | | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. | | | 7-REVISE CONNECTOR TC-1 ON ROOF FRAMING | | | PLAN AT FRONT ELEVATION. TC CONNECTORS | | | ARE FOR WOOD TO CONCRETE. NEED WOOD TO | | | WOOD CONNECTORS AT FRAMED WALL. SEC. | | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
|