| Plan Review Notes For Permit 02110846 |
| Permit Number |
02110846 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-12-12 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-PROVIDE COMPLETE INFORMATION FOR STORM | | | SHUTTERS UNDER A SEPARATE PERMIT. | | | 2-FLOOD ZONE A8. NEED THE ELEVATION | | | CERTIFICATE. | | | 3-2ND FLOOR FRAMING PLAN: | | | PROVIDE DRAFSTOPPING AT AREAS NOT TO | | | EXCEED 500 S.F. SEC. 2305.2.2 FBC 2001 | | | 4-SPECIFY SIZE OF ANCHOR BOLT AND WASHER | | | FOR GARAGE STRUCTURAL BUCK DETAIL. | | | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. | | | 5-34SH WINDOWS DON'T PROVIDE THE 24" MIN | | | CLEAR HEIGHT. ALSO, MAKE SURE THAT | | | 24+5 SH WINDOWS PROVIDE THE 5.7 S.F. | | | MIN. CLEAR OPENING REQUIRED BY SECTION | | | 105.4.4 FBC 2001. | | | 6-DETAIL S21 DOESN'T WORK FOR WOOD COL. | | | P1 LOCATED AT GARAGE CORNER. REVISE/ | | | CLARIFY AS REQUIRED. SEC. 104.2.1.2 | | | CITY AMENDMENTS TO FBC 2001. | | | 7-REVISE CONNECTOR TC-1 SPECIFIED ON | | | ROOF FRAMING PLAN AT FRONT ELEVATION. | | | NEED WOOD TO WOOD HURRICANE CONNECTOR. | | | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
|