2002-12-12 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 2-FLOOD ZONE A8. NEED THE ELEVATION
 CERTIFICATE.
 3-2ND FLOOR FRAMING PLAN:
 PROVIDE DRAFSTOPPING AT AREAS NOT TO
 EXCEED 500 S.F. SEC. 2305.2.2 FBC 2001
 4-SPECIFY SIZE OF ANCHOR BOLT AND WASHER
 FOR GARAGE STRUCTURAL BUCK DETAIL.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 5-34SH WINDOWS DON'T PROVIDE THE 24" MIN
 CLEAR HEIGHT. ALSO, MAKE SURE THAT
 24+5 SH WINDOWS PROVIDE THE 5.7 S.F.
 MIN. CLEAR OPENING REQUIRED BY SECTION
 105.4.4 FBC 2001.
 6-DETAIL S21 DOESN'T WORK FOR WOOD COL.
 P1 LOCATED AT GARAGE CORNER. REVISE/
 CLARIFY AS REQUIRED. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 7-REVISE CONNECTOR TC-1 SPECIFIED ON
 ROOF FRAMING PLAN AT FRONT ELEVATION.
 NEED WOOD TO WOOD HURRICANE CONNECTOR.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.