| Plan Review Notes For Permit 02110845 |
| Permit Number |
02110845 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-12-09 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | 1) PER TABLE 403.1 A DRINKING FOUNTAIN | | | AND A SERVICE SINK IS REQUIRED IN EACH | | | WAREHOUSE "A" AND "B". IF WATER COOLERS | | | ARE USED PER SECTION 410.1 THEN THEY | | | SHALL BE ARI-1010 COMPLIANT AND MANUF. | | | INFO IS REQUIRED. IF WAREHOUSE IS DIVID- | | | ED FURTHER THAN A DRINKING FOUNTAIN AND | | | SERVICE SINK SHALL BE REQUIRED FOR EACH | | | SPACE. | | | 2) RPZ BACKFLOW PREVENTER IS REQUIRED ON | | | EACH WATER SERVICE. | | | 3) PLEASE PROVIDE A WATER RISER DIAGRAM. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|