| Plan Review Notes For Permit 02110831 |
| Permit Number |
02110831 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-12-19 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-PROVIDE COMPLETE INFORMATION FOR STORM | | | SHUTTERS UNDER A SEPARATE PERMIT. | | | 2-FLOOD ZONE A8. NEED TO PROVIDE THE | | | ELEVATION CERTIFICATE. | | | 3-CLARIFY DETAIL S21. PROVIDE CLEAR FOR | | | COLUMN BETWEEN GARAGE AND STAIRWAY | | | SHOWING HOW IS THE TOP CONNECTOR | | | RECEIVING THE TWO GIRDER TRUSSES. SEC. | | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. | | | 4-REVISE CONNECTOR TC-1 SPECIFIED AT | | | FRONT ELEVATION ON ROOF FRAMING PLAN. | | | NEED WOOD TO WOOD CONNECTOR FOR FRAMED | | | WALL. SEC. 104.2.1.2 CITY AMENDMENTS | | | TO FBC 2001. | | | 5-PROVIDE SPECIFICATIONS ON STRUCTURAL | | | WALL SECTIONS FOR FIRECUT REQUIREMENTS | | | TO COMPLY WITH SEC. 2305.4 FBC 2001. | | | 6-REVISE STAIRS TOP DETAIL ON SHEET A-4 | | | TO MATCH FRAMING PLAN AND SPECIFY | | | FIREBLOCKING. SEC. 2305.1.4 FBC 2001. |
|