| 2002-11-18 00:00:00 | UNSAT |
| | ~~~~~ |
| | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| | PLEASE PROVIDE THE FOLLOWING |
| | INFORMATION,MAKE NECESSARY CHANGES TO |
| | THE PLAN AND RESUBMIT FOR REVIEW. |
| | |
| | 1} PLEASE NOTE THAT ALL PLANS |
| | DRAWN BY AN ARCHITECT/ENGINEER CONTAIN- |
| | ING A TITLE BLOCK, MUST BE SIGNED, |
| | DATEDAND SEALED BY THE ARCH/ENGINEER OF |
| | RECORD. PER FS/FAC 481.221 & 471.025 |
| | |
| | 2} PLEASE SUBMIT RISER DIAGRAMS WITH ALL |
| | PANELS,DISCONNECTS AND GROUNDING |
| | SYSTEMS TO BE USED. |
| | |
| | 3} PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 4} SHOW LOCATIONS OF DISCONNECTS,PANELS |
| | AND GROUNDING MEANS AT ALL LOCATIONS ,ON |
| | PLANS. |
| | |
| | 5} INCLUDE SMALL APPLIANCE CIRCUITS IN |
| | LOAD CALCULATIONS PER 210-11(C)(1). |
| | |
| | 6} PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S). PER 210-11-C-3 |
| | MUST BE 20A AND #12AWG,ON PANEL SCHEDULE |
| | |
| | 7} PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CIRCUITS ON PANEL |
| | SCHEDULE,PER 210-12. |
| | |
| | 8} PLEASE SUBMIT LOAD CALCAULATIONS PER |
| | 220,215-5. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/659/8096 EXT.8392 |