| Plan Review Notes For Permit 02110785 |
| Permit Number |
02110785 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-11-21 00:00:00 | ****************** UNSAT ************** | | | | | | 1)NOTE: PLEASE SUPPLY ENGINEERING FOR | | | LIGHT POLE WIND LOADING PER FBC 140MPH. | | | | | | 2)NOTE: PLEASE NOTE, ALL CONTINUOUS | | | LOADS ARE TO BE SHOWN AT 125%.215-3, | | | 230-42. | | | | | | 3)NOTE: PLEASE PROVIDE COPY OF CONTRACT | | | TO VERIFY VALUE OF WORK. PLEASE NOTE, | | | UNDER ADMINISTRATIVE CODE 104.6.5. VALUE | | | IS ALL LABOR AND MATERIALS EVEN IF | | | OWNER SUPPLIED. | | | | | | PLEASE NOTE, PLANS WERE ONLY SUBMITTED | | | FOR PLAN REVIEW AND WOULD NEED TO HAVE | | | AN ELECTRICAL CONTRACTOR SIGNED ON FOR | | | ALL ELECTRICAL WORK TO BE DONE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLANREVIEW | | | 561-659-8096 EXT 8372 |
|