Plan Review Notes
Plan Review Notes For Permit 02110771
Permit Number 02110771
Review Stop R
Sequence Number 1
Notes
Date Text
2002-12-16 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) PROVIDE (2) COPIES OF SITE PLAN
 INDICATING THE LOCATION OF THE STRUCTURE
 ON THE LOT SIGNED AND SEALED BY THE
 DESIGNER OF RECORD OR (2) COPIES OF A
 SIGNED AND SEALED SURVEY SHOWING THE
 STRUCTURES LOCATION.
  
 3)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 4) INDICATE THE NEGATIVE AND POSITIVE
 WINDLOAD PRESSURES FOR ALL EXTERIOR
 WINDOW AND DOOR OPENINGS. CLARIFY THE
 DESIGN WIND PRESSURES ON A4. ARE THESE
 WORST CASE DESIGN PRESSURES?
  
 5) SPECIFY THE ROOF SHEATHING THICKNESS
 AND NAILING REQUIREMENTS.SEE CITY OF WPB
 AMENDMENTS TO FBC TABLE 2306.1.
  
 6) PROVIDE BUCK ATTACHMENT DETAILS FOR
 WINDOWS AND DOORS. SEE FBC 1707.4.4.2.
  
 7)INDICATE ATTIC VENTILATION. FBC 2309.7
  
 8) INDICATE ACCESS TO ATTIC SPACE.
 FBC 2309.6.
  
 9) PROVIDE A WALL/CEILING SECTION
 SHOWING FURRING, INSULATION, FIREBLOCK-
 ING, INTERIOR FINISH, TIE BEAM, ETC.
  
 10) SPECIFY WINDOW TYPES AND SIZES ON
 THE PLANS. BEDROOM WINDOWS ARE REQUIRED
 TO PROVIDE EMERGENCY EGRESS AND HAVE
 SPECIFIC CLEAR OPENING SIZES AND AREA
 SEE FBC 1005.4.
  
 11) SAFETY GLASS IS REQUIRED IN THE BATH
 ROOM WINDOWS THAT ARE IN THE TUB AND ARE
 WITHIN 3 FEET HORIZONTALLY OF THE SHOWER
 PER FBC 2405.2.1.
  
 12) SAFETY GLASS IS REQUIRED IN THE
 WINDOWS BESIDE THE FRONT DOOR, WHICH ARE
 WITHIN 2 FEET OF THE DOOR. SEE FBC
 2405.2.1.
  
 13) INDICATE ON THE PLANS THAT THE
 FINISH FLOOR ELEVATION IS A MINIMUM OF
 4"ABOVE FINISH GRADE AND THE BOTTOM OF
 THE FOOTING IS A MINIMUM OF 12" BELOW
 GRADE. SEE CITY AMENDMENTS 1804.1.7 AND
 FBC 1804.1.3.
  
 14) PROVIDE A DETAIL OF THE BOND BEAM
 INDICATING THE SIZE AND NUMBER OF
 HORIZONTAL REINFORCEMENT.
  
 15) SPECIFY THE SIZE AND NUMBER OF
 VERTICAL REINFORCEMENT IN EACH FILLED
 CELL.
  
 16) SPECIFY THE LINTELS ABOVE THE DOORS
 AND WINDOWS. PROVIDE A LINTEL SCHEDULE.
  
 17) PROVIDE DETAILS FOR CONSTRUCTING
 ARCH OPENING ABOVE FRENCH DOORS,PARAPET
 WALLS, ETC.
  
 18) SPECIFY CONNECTORS FOR ROOF TRUSSES.
  
 19) SPECIFY THE CEILING HEIGHTS, BEAM
 HEIGHTS, ROOF HEIGHT, ETC.
  
 20) INDICATE THE ROOF SLOPE, SCUPPER
 LOCATION, GUTTER & DOWN SPOUT LOCATIONS,
 ETC. SEE FBC 1804.1.6
  
 21) INDICATE TERMITE TREATMENT ON PLANS
 PER FBC 1816.1.
  
 22) INDICATE ON PLANS THAT WWM IN THE
 SLAB WILL BE SUPPORTED AS REQUIRED BY
 FBC 1909.3.
  
 24) THE ENERGY CALCULATION FORM IS
 REQUIRED TO BE SIGNED AND DATED BY THE
 OWNER/AGENT.
  
 25) SHEETS ONE AND TWO OF THE DRAWINGS
 SUBMITTED WITH THE PRODUCT APPROVAL FOR
 THE STANLEY OUTSWING OPAQUE STEEL DOOR
 DO NOT BELONG WITH THIS PRODUCT APPROVAL
 THE NOA NUMBER, DATE, DRAWING NUMBERS
 ARE DIFFERENT. SUBMIT THE COMPLETE
 PACKAGE WITH THE CORRECT DRAWINGS.
  
 26) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - CIRCLE TOP FIXED GLASS WINDOWS
 - FRENCH DOORS
 - HORIZONTAL & VERTICAL STRUCTURAL
 MULLIONS
 - FRONT DOOR
  
 27) IF YOU ARE USING IMPACT GLAZING,
 SPECIFY THIS ON THE PLANS AND HIGHLIGHT
 OR CIRCLE IT ON THE PRODUCT APPROVAL.
  
 28)PROVIDE (2) PRODUCT APPROVALS, KEY
 PLANS AND INSTALLATION SCHEDULES
 INDICATING THE SPECIFIC TYPES OF ANCHORS
 TO BE USED FOR STORM PANELS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202