| 2002-12-16 00:00:00 | BUILDING DENIED |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) PROVIDE (2) COPIES OF SITE PLAN |
| | INDICATING THE LOCATION OF THE STRUCTURE |
| | ON THE LOT SIGNED AND SEALED BY THE |
| | DESIGNER OF RECORD OR (2) COPIES OF A |
| | SIGNED AND SEALED SURVEY SHOWING THE |
| | STRUCTURES LOCATION. |
| | |
| | 3)FL. BLD CODE 1606.1.7 THE FOLLOWING |
| | INFORMATION RELATED TO WIND SHALL BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | |
| | 4) INDICATE THE NEGATIVE AND POSITIVE |
| | WINDLOAD PRESSURES FOR ALL EXTERIOR |
| | WINDOW AND DOOR OPENINGS. CLARIFY THE |
| | DESIGN WIND PRESSURES ON A4. ARE THESE |
| | WORST CASE DESIGN PRESSURES? |
| | |
| | 5) SPECIFY THE ROOF SHEATHING THICKNESS |
| | AND NAILING REQUIREMENTS.SEE CITY OF WPB |
| | AMENDMENTS TO FBC TABLE 2306.1. |
| | |
| | 6) PROVIDE BUCK ATTACHMENT DETAILS FOR |
| | WINDOWS AND DOORS. SEE FBC 1707.4.4.2. |
| | |
| | 7)INDICATE ATTIC VENTILATION. FBC 2309.7 |
| | |
| | 8) INDICATE ACCESS TO ATTIC SPACE. |
| | FBC 2309.6. |
| | |
| | 9) PROVIDE A WALL/CEILING SECTION |
| | SHOWING FURRING, INSULATION, FIREBLOCK- |
| | ING, INTERIOR FINISH, TIE BEAM, ETC. |
| | |
| | 10) SPECIFY WINDOW TYPES AND SIZES ON |
| | THE PLANS. BEDROOM WINDOWS ARE REQUIRED |
| | TO PROVIDE EMERGENCY EGRESS AND HAVE |
| | SPECIFIC CLEAR OPENING SIZES AND AREA |
| | SEE FBC 1005.4. |
| | |
| | 11) SAFETY GLASS IS REQUIRED IN THE BATH |
| | ROOM WINDOWS THAT ARE IN THE TUB AND ARE |
| | WITHIN 3 FEET HORIZONTALLY OF THE SHOWER |
| | PER FBC 2405.2.1. |
| | |
| | 12) SAFETY GLASS IS REQUIRED IN THE |
| | WINDOWS BESIDE THE FRONT DOOR, WHICH ARE |
| | WITHIN 2 FEET OF THE DOOR. SEE FBC |
| | 2405.2.1. |
| | |
| | 13) INDICATE ON THE PLANS THAT THE |
| | FINISH FLOOR ELEVATION IS A MINIMUM OF |
| | 4"ABOVE FINISH GRADE AND THE BOTTOM OF |
| | THE FOOTING IS A MINIMUM OF 12" BELOW |
| | GRADE. SEE CITY AMENDMENTS 1804.1.7 AND |
| | FBC 1804.1.3. |
| | |
| | 14) PROVIDE A DETAIL OF THE BOND BEAM |
| | INDICATING THE SIZE AND NUMBER OF |
| | HORIZONTAL REINFORCEMENT. |
| | |
| | 15) SPECIFY THE SIZE AND NUMBER OF |
| | VERTICAL REINFORCEMENT IN EACH FILLED |
| | CELL. |
| | |
| | 16) SPECIFY THE LINTELS ABOVE THE DOORS |
| | AND WINDOWS. PROVIDE A LINTEL SCHEDULE. |
| | |
| | 17) PROVIDE DETAILS FOR CONSTRUCTING |
| | ARCH OPENING ABOVE FRENCH DOORS,PARAPET |
| | WALLS, ETC. |
| | |
| | 18) SPECIFY CONNECTORS FOR ROOF TRUSSES. |
| | |
| | 19) SPECIFY THE CEILING HEIGHTS, BEAM |
| | HEIGHTS, ROOF HEIGHT, ETC. |
| | |
| | 20) INDICATE THE ROOF SLOPE, SCUPPER |
| | LOCATION, GUTTER & DOWN SPOUT LOCATIONS, |
| | ETC. SEE FBC 1804.1.6 |
| | |
| | 21) INDICATE TERMITE TREATMENT ON PLANS |
| | PER FBC 1816.1. |
| | |
| | 22) INDICATE ON PLANS THAT WWM IN THE |
| | SLAB WILL BE SUPPORTED AS REQUIRED BY |
| | FBC 1909.3. |
| | |
| | 24) THE ENERGY CALCULATION FORM IS |
| | REQUIRED TO BE SIGNED AND DATED BY THE |
| | OWNER/AGENT. |
| | |
| | 25) SHEETS ONE AND TWO OF THE DRAWINGS |
| | SUBMITTED WITH THE PRODUCT APPROVAL FOR |
| | THE STANLEY OUTSWING OPAQUE STEEL DOOR |
| | DO NOT BELONG WITH THIS PRODUCT APPROVAL |
| | THE NOA NUMBER, DATE, DRAWING NUMBERS |
| | ARE DIFFERENT. SUBMIT THE COMPLETE |
| | PACKAGE WITH THE CORRECT DRAWINGS. |
| | |
| | 26) PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - CIRCLE TOP FIXED GLASS WINDOWS |
| | - FRENCH DOORS |
| | - HORIZONTAL & VERTICAL STRUCTURAL |
| | MULLIONS |
| | - FRONT DOOR |
| | |
| | 27) IF YOU ARE USING IMPACT GLAZING, |
| | SPECIFY THIS ON THE PLANS AND HIGHLIGHT |
| | OR CIRCLE IT ON THE PRODUCT APPROVAL. |
| | |
| | 28)PROVIDE (2) PRODUCT APPROVALS, KEY |
| | PLANS AND INSTALLATION SCHEDULES |
| | INDICATING THE SPECIFIC TYPES OF ANCHORS |
| | TO BE USED FOR STORM PANELS. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |